Omron S8AS User Manual page 115

Smart power supply
Table of Contents

Advertisement

Frame Structure
Parameters
Variable Type 81
Address
0000
Undervoltage detection threshold (V)
0002
Over-temperature output threshold (°C)
0004
Protection level
0005
Remaining life threshold
0006
Alarm reset setting
0007
External tripping input function setting
Address
0010
Current tripping type for branch output 1
0011
Current tripping type for branch output 2
0012
Current tripping type for branch output 3
0013
Current tripping type for branch output 4
0014
Current tripping type for branch output 5
0015
Current tripping type for branch output 6
0016
Current tripping type for branch output 7
0017
Current tripping type for branch output 8
Address
0020
Current tripping threshold for branch out-
put 1
0021
Current tripping threshold for branch out-
put 2
0022
Current tripping threshold for branch out-
put 3
0023
Current tripping threshold for branch out-
put 4
0024
Current tripping threshold for branch out-
put 5
0025
Current tripping threshold for branch out-
put 6
0026
Current tripping threshold for branch out-
put 7
0027
Current tripping threshold for branch out-
put 8
Address
0050
Startup sequence for branch output 1
0051
Startup sequence for branch output 2
0052
Startup sequence for branch output 3
0053
Startup sequence for branch output 4
0054
Startup sequence for branch output 5
0055
Startup sequence for branch output 6
0056
Startup sequence for branch output 7
0057
Startup sequence for branch output 8
Name
00B4 to 0108 (18.0 to 26.4 V)
0019 to 005A (25 to 90°C)
0000 to 0002
(0: R/W allowed; 1: Limited R/
W; 2: Limited read-only)
0000 to 0032 (0.0 to 5.0
years)
0000 to 0001 (0: Key, 1: Key +
Power ON)
0000 to 0001 (0: Edge, 1:
Level)
Name
0000 or 0002
(0: Standard; 1: Instanta-
neous, 2: Extended)
Name
0005 to 0026 (0.5 to 3.8 A)
Name
0000 to 03E7
(0: Disabled, or 0.1 to 99.9 s)
Section 6-2
Data range
Data range
Data range
Data range
97