Basic Function Details
Current Tripping Characteristics
32
Standard Detection
Time (ms)
Setting
range
100
60
20
0.5
Instantaneous Detection
Time (ms)
Setting
range
20
0.5
Extended Detection
Time (ms)
Setting
range
1,000
60
20
0.5
Note The S8AS contains a current-restricting circuit that prevents a cur-
rent above a specific value from flowing. The current is thus restrict-
ed during the time required to cut off the output.
Note
After sampling and converting each branch output's current every 1 ms, the
S8AS processes the values in the CPU and controls the branch output cut-
offs. This method achieves high-speed, high-accuracy tripping. In addition, to
minimize the effects of excessive currents caused by short-circuits, the S8AS
is equipped with built-in current-limiting circuits. Consequently, there is a
Tripping region
16
19
3.8
11
Tripping region
19
3.8
Tripping region
Current-
limiting
by internal
circuits
19
16
3.8
11
Section 2-4
Tolerance of current trip-
ping alarm threshold:
±0.3 A. When the trip-
Current-
ping current (0.5 to
limiting
by internal
3.8 A) is detected, it is
circuits
cut off within 100 ms.
Current (A)
Tolerance of current trip-
ping alarm threshold:
±0.3 A. When the trip-
Current-
ping current (0.5 to
limiting
3.8 A) is detected, it is
by internal
cut off within 20 ms.
circuits
Current (A)
Tolerance of current trip-
ping alarm threshold:
±0.3 A.When the trip-
ping current (0.5 to
3.8 A) is detected, it is
cut off within 1,000 ms.
Current (A)