Seven-segment Error Codes

7-2
Seven-segment Error Codes
Error Display List
Seven-segment
Error
display
code
erp
ERP
.
---
alp
ALP
e98
E98
e97
E97
e96
E96
e95
E95
e94
E94
e00
E00
e01
E01
e02
E02
e03
E03
e10
E10
a 10
A10
a 11
A11
a 12
A12
a21
A21
a23
A23
a23/hot
A23/
HOT
a30
A30
114
Meaning
Memory error on
These are S8AS system errors.
power supply side
When one of these error codes is displayed, check the system config-
uration and clear the error, and then turn the power supply OFF and
S8AS hardware error
ON again.
Power supply voltage
If the error code persists, contact your OMRON representative
error
regarding the error.
RAM error
EEPROM read error
EEPROM write error
Internal communica-
tions error
Short circuit failure
EEPROM initialization
error
EEPROM error
Model error
Factory default detec-
tion mode
Data other than com-
There is an error in the parameter
munications data is
settings.
corrupted.
Abnormal voltage trip-
The power supply voltage
ping
exceeded 28.8 V.
Abnormal current trip-
The branch output's current
ping
exceeded the current tripping
threshold.
Total current tripping
All branch outputs were cutoff
because the total current and the
power-ON time exceeded the
abnormal total current tripping
conditions.
Undervoltage alarm
The output voltage dropped
below the undervoltage detection
threshold.
Maintenance forecast
The replacement time calculated
monitor output
by the S8AS is lower than the
notification time.
Overheating alarm
The S8AS is overheated
Over-temperature out-
The S8AS's internal temperature
put
exceeded the over-temperature
output threshold.
• When two or more errors occur simultaneously, the higher priority error
(higher in the table above) will be displayed.
Probable cause and remedy
Press the Mode Key to switch to
the parameter initialization dis-
play. After initializing the parame-
ters, set them again.
This error is treated as a system
error for the S8AS-24006N/
48008N.
Check the power supply voltage.
Check whether the connected
device is correct and check
whether the set value is appropri-
ate.
Check whether the connected
devices are suitable and operat-
ing within the total current limit.
Check the power supply voltage
and the set value.
Indicates that the replacement
time is approaching.
Take steps to reduce the internal
temperature.
Check for a high ambient temper-
ature and check the setting of the
over-temperature output thresh-
old.
Take steps to reduce the temper-
ature in the control panel.