Compoway/F Communications Specifications - Omron S8AS User Manual

Smart power supply
Table of Contents

Advertisement

CompoWay/F Communications Specifications

6-1

CompoWay/F Communications Specifications

Connecting to the
Network
Communications
Specifications
88
The S8AS-@ @ @ @ @ R is equipped with an RS-485 port, which allows remote
monitoring and remote operations over networks, such as setting parameters,
connecting/disconnecting outputs, and clearing errors.
Refer to 3-4 RS-485 Port Wiring for details on connecting the communications
cable.
Connection configuration
Communications method
Synchronization method
Baud rate
Transmission code
Data length
Stop bits
Error detection
Flow control
Retry function
Communications cable
1:n connection
RS-485
Start-stop synchronization
4,800 or 9,600 bps (Default value: 9,600 bps)
ASCII
7 or 8 bits (Default value: 7 bits)
1 or 2 bits (Default value: 2 bits)
Vertical parity: None, even, or odd (Default value: Even)
BCC (block check character)
None
None