Omron S8AS User Manual page 30

Smart power supply
Table of Contents

Advertisement

Table of Basic Functions
Alarm Output and Error
Display Functions
12
Symbol
Output
name
TRP
Tripping
alarm output
LOW
Undervolt-
age detec-
tion output
LFE
Mainte-
nance fore-
cast monitor
output
Overheating
alarm (See
note 2.)
TMP
Over-tem-
perature
output
Note
(1) In this manual, the lifetime of the Unit is expressed in years.
(2) If the overheating alarm stays on for more than 3 hours, it can no longer
be cleared.
Operation
Abnormal Voltage Tripping Operation
When the output voltage exceeds 28.8 VDC,
all branch outputs are cut off and the TRP
output is turned ON. (The photoswitch output
is turned OFF.)
Abnormal Current Tripping Operation
When the branch output current exceeds the
set value, the branch output is cut off and the
TRP output is turned ON. (The photoswitch
output is turned OFF.)
Volt-amperage (VA) Tripping Operation
When the voltage times the current (VA)
exceeds the set value for a specified amount
of time, the branch output is cut off and the
TRP output is turned ON. (The photoswitch
output is turned OFF.)
Abnormal Total Current Tripping Operation
When the total output current exceeds the set
value, all branch outputs are cut off and the
TRP output is turned ON. (The photoswitch
output is turned OFF.)
Indicates that there are branch outputs that
are not connected. This error is not output in
any mode other than Test Mode.
When there is a disconnected branch output
in Test Mode, the TRP output is turned ON.
(The photoswitch output is turned OFF.)
Setting range: 18.0 to 26.4 VDC (0.1-V incre-
ments)
When the output voltage falls below the set
value, the LOW output is turned ON. (The
photoswitch output is turned OFF.)
Setting range: 0.0 to 5.0 years (0.5-yr incre-
ments) (See note 1.)
When the internally calculated replacement
time falls below the set value, the LFE output
is turned ON. (The photoswitch output is
turned OFF.)
LFE output is turned ON (the photoswitch out-
put is turned OFF) when the replacement
time cannot be calculated correctly due to rise
in internal temperature.
Setting range: 25 to 90°C (1°C increments)
When the temperature falls below the set
value minus 3°C, the TMP output and the
error code shown on the seven-segment dis-
play will be automatically cleared.
Section 1-3
Error code
displayed
A10
A11/Current
(alternating)
A11/Current
(alternating)
A12
---
A21/Voltage
(alternating)
A23/
Replace-
ment time
(alternating)
A23/HOT
(alternating)
A30/Temper-
ature (alter-
nating)