Power Supply and Input/Output Wiring
Wiring the External
Outputs and External
Tripping Input
50
• When inserting the wire, make sure that the stripped portion of the wire is
fully inserted and not left exposed.
• After completing a connection, lightly pull on the wire to make sure that it
has been locked in properly.
The TRP, LOW, LFE, and TMP outputs operate as normally closed outputs,
which are OFF when the power is OFF, ON during normal operation, and OFF
when an error has occurred. If you want to use these an external output as a
normally open output, invert the signal through an auxiliary relay (X). When
doing so, the alarm may turn ON momentarily when the power supply is
turned ON. To prevent this, delay the signal through the delay relay (TR).
The branch output is cut off when the External Tripping Input (TRG) is ON
(connected).
TRP
LOW
LFE
TR
X1
X2
X3
Delay Relay
No.
Name
1
TRP
Tripping Alarm
Output
2
LOW
Undervoltage
Detection Output
3
LFE
Maintenance
Forecast Monitor
Output
4
TMP
Over-temperature
Output
5
COM
Output Common
6
TRG (+) External Tripping
Input
7
TRG (−)
TMP
COM TRG(+) TRG(−)
*
X4
Tripping Input
* Output terminals do not have polarity.
The photoswitch output turns OFF when the
branch output is cut off due to an abnormal
voltage or abnormal current.
The photoswitch output turns OFF when the
output voltage drops below the set value.
The photoswitch output turns OFF when the
estimated replacement time drops below the
set value.
The photoswitch output turns OFF when the
S8AS's internal temperature exceeds the
over-temperature output threshold.
Common terminal for the four outputs
described above.
Branch outputs can be cut off from an exter-
nal operation. (The shutdown sequence is
applied in this case.)
Section 3-3
TR
X1 X2
X3
X4
Function