Specifications
Item
Model
Func-
Over-temper-
Over-tempera-
tions
ature detec-
ture
tion function
Over-tempera-
ture output
Display func-
Output voltage
tions
display
Output current
display
Maintenance
forecast moni-
tor display
Temperature
display
External Tripping Input
Startup sequence
Shutdown sequence
Communications
Sampling period
Parallel connection
Series connection
S8AS-24006
Setting range: 25 to 90°C
(in 1°C increments)
Photoswitch output
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max.,
Residual voltage: 2 V max.
Display range: 17.0 to 30.0 V
Display accuracy: 2% rdg ±1 digit max.
Branch output display range: 0.0 to 4.0 A
Peak output current display range: 0.0 to 20.0 A
Total current display range: 0.0 to 40.0 A
Display accuracy: 5% FS (4 A) ±1 digit max.
Display range: FUL (Full)/HLF (Half)/0.0 to 5.0 yr
Display range: −20 to 100°C
Display accuracy: 2°C ±1 digit max.
The input can be enabled
or disabled for each
branch output.
19.2 to 30 VDC, mini-
mum signal width: 10 ms,
tripping after input within
20 ms + the shutdown
sequence set time
Setting range: 0.0 to
99.9 s in 0.1-s incre-
ments
Setting range: 0.0 to
99.9 s in 0.1-s incre-
ments
Not supported
1 ms
Not supported.
Not supported.
S8AS-24006N
90°C (Cannot be
changed.)
All branch outputs:
Enabled (Cannot be
changed.)
19.2 to 30 VDC, mini-
mum signal width: 10 ms,
tripping after input within
20 ms + the shutdown
sequence set time
Branch output 1: 0.0 s
(Cannot be changed.)
Branch output 2: 0.4 s
(Cannot be changed.)
Branch output 3: 0.8 s
(Cannot be changed.)
Branch output 4: 1.2 s
(Cannot be changed.)
Branch output 5: 1.6 s
(Cannot be changed.)
Branch output 6: 2.0 s
(Cannot be changed.)
All branch outputs:
0.0 s (Cannot be
changed.)
Section 2-3
S8AS-24006R
Setting range: 25 to 90°C
(in 1°C increments)
The input can be enabled
or disabled for each
branch output.
19.2 to 30 VDC, mini-
mum signal width: 10 ms,
tripping after input within
20 ms + the shutdown
sequence set time
Setting range: 0.0 to
99.9 s in 0.1-s incre-
ments
Setting range: 0.0 to
99.9 s in 0.1-s incre-
ments
Supported (RS-485)
23