Omron S8AS User Manual page 76

Smart power supply
Table of Contents

Advertisement

Switching the Operating Mode
Flashing
58
Note
The procedure for initializing parameters is given below. (Parameters cannot
be initialized for the S8AS-24006N/48008N.)
Press the
to the parameter initialization display.
i n i
If the
performed from this display.
(The S8AS will automatically return to the Parameter Initialization Dis-
play (INI) if no key is pressed within 3 s.)
n o
Press the
(
)
be initialized if the
(The S8AS will automatically return to the Parameter Initialization Dis-
play (INI) if no key is pressed within 3 s.)
y e s
Press the
INI will flash on the display while parameters are being initialized. When
the display stops flashing, all parameters will have been initialized.
i n i
i n i
The operating mode will change to Run Mode.
2 4. 0
After the parameters have been initialized, the default settings will be in effect
and the initial power-ON status will be used.
• The operating mode will be Run Mode.
• All branch outputs will be connected.
• Protection level 1 will be used.
Key from the initialize display (INI). The S8AS will switch
Key is pressed, NO will be displayed. Initialization cannot be
Key. The display will change to YES. The parameters will
Key is pressed from this display.
Key to start initializing parameters.
Section 4-2