Special Settings and Communications Settings
Setting the Shutdown Sequence: DWS (Shutdown Sequence)
d w s
Switch to the
Tripping Input
Trigger Setting
(TRG).
The Shutdown Sequence Setting (DWS) will be displayed if the Up (SEL) Key
(
) is pressed from the Startup Sequence Setting Display. The shutdown
sequence sets the shutdown sequence time for each branch output. (The
branch output that was most recently modified will be the current branch out-
put regardless of the operating mode.)
(To change the
branch output)
* 0
% 5
(Returns to DWS display.)
Note
The shutdown sequence function sets the time that the S8AS waits before
cutting off each branch output when the branch outputs are cut off by the
external tripping input or communications. For details on the startup
sequence, refer to 2-6 Shutdown Sequence Function.
d w s
Press the
Key to display the Shutdown Sequence
Time Set Value (SV) for the current branch output. The SV
can be changed by pressing the
setting range is 0.0 to 99.9 s (0.1-s increments).
Change the SV with the
The S8AS will automatically return to the DWS display if
no key is pressed within 3 s.
If the
or
Key is pressed for more than 2 s, the SV
will change in 1.0-s increments instead of 0.1-s incre-
ments.
When the
Key is pressed, the SV display will flash.
When the flashing stops, the new setting will be saved and
the S8AS will return to DWS display.
• If you want to confirm the new setting, press the
again from the DWS display.
• To change the shutdown sequence of other branch out-
puts, press the
Key from the DWS display to select
the desired branch output, and then follow the procedures
to change the settings.
Section 4-7
and
Keys. The
and
Keys.
Key
67