Shared Parameter Settings - Omron S8AS User Manual

Smart power supply
Table of Contents

Advertisement

Shared Parameter Settings

4-6

Shared Parameter Settings

Setting the Undervoltage Detection Output Value: V-U (Voltage Under)
V - u
Switch to the
Maintenance
Forecast Moni-
tor Detection
Threshold Set-
ting (LFE).
Standard (usu)
Instantaneous (ins) When the current exceeds the tripping threshold for more than 10
Extended (lng)
After setting the abnormal current tripping threshold and tripping type for all
branch outputs, press the Up (SEL) Key (
Detection Threshold Display (V-U).
This parameter sets the undervoltage detection threshold.
2 * 0
2 ! 5
(Returns to V-U display.)
Note
If the voltage remains below the detection threshold for 80 ms, the photo-
switch output for the Undervoltage Detection Output (LOW) will turn OFF. At
the same time, the seven-segment display will show the error code A21 and
the voltage value.
The alarm output can be cleared after the voltage rises above the threshold
+0.3 V for more than 500 ms.
When the current exceeds the tripping threshold for more than 80
ms, the branch output is cut off and the Tripping Alarm Output (TRP)
is turned OFF. The output will be cut off within 100 ms.
ms, the branch output is cut off and the Tripping Alarm Output (TRP)
is turned OFF. The output will be cut off within 20 ms.
When the current exceeds the tripping threshold for more than 980
ms, the branch output is cut off and the Tripping Alarm Output (TRP)
is turned OFF. The output will be cut off within 1,000 ms.
Press the
Key to display the undervoltage detec-
tion's set value (SV).
The SV can be changed by pressing the
Keys.
The setting range is 18.0 to 26.4 V (0.1-V increments).
• If the
or
SV will change in 1.0-V increments instead of 0.1-V
increments.
Change the SV with the
The S8AS will automatically return to the V-U display if
no key is pressed within 3 s.
When the
Key is pressed, the SV display will flash.
When the flashing stops, the new setting will be saved
and the S8AS will return to V-U display.
If you want to confirm the new setting, press the
again from the V-U display.
Section 4-6
) to go to the Undervoltage
Key is pressed for more than 2 s, the
and
Keys.
and
Key
63