Omron S8AS User Manual page 29

Smart power supply
Table of Contents

Advertisement

Table of Basic Functions
Tripping/
Alarm Functions
Tripping Functions
Data name
Protection level
Reset operation
There are three ways for the S8AS's tripping function to operate:
• Tripping by user-set parameters
• Tripping by the S8AS's system monitor
• Tripping by external operation
The external signal outputs include the Tripping Alarm Output (TRP), Under-
voltage Detection Output (LOW), Maintenance Forecast Monitor Output
(LFE), and Over-temperature Output (TMP).
Setting
Abnormal volt-
age tripping
Short-circuit
current
tripping
Abnormal total
current trip-
ping
Abnormal
current
tripping
(See note 1.)
External trip-
ping input
Note
(1) The tripping function operates within 100 ms when the S8AS is set to
standard detection, within 20 ms when it is set to instantaneous detec-
tion, and within 1,000 ms when it is set to extended detection.
(2) The TRG signal applies only to the branch outputs for which the external
tripping input is enabled. For details, refer to 2-7 External Tripping Input
Function.
Detail
The Protection Level function can restrict parameter
read/write access by setting one of three levels. The
default protection level is level 1.
The tripping alarm output and alarm output can be
cleared after removing the cause of the alarm by the
following two methods.
• KEY: RST Key only.
• ALL: RST Key or turning power OFF and ON again.
Operating range
Output cut off for voltage over 28.8 VDC. None
Output cut off at 16 A for 20 ms max.
Output cut off at 11 A for 60 ms max.
Output cut off when the sum of all branch
output currents exceeds the set value for
a specific length of time.
0.5 to 3.8 A (in 0.1-A increments)
Select from standard, instantaneous, and extended
detection methods.
• External input signal (TRG) ON
• Tripping by communications.
Section 1-3
Setting
range
0 to 2
KEY, ALL
Parameter
Outputs
settings
cut off
All branch
outputs
None
Individual
branch out-
put
None
All branch
outputs
Individual
branch out-
put
Specified
output
(See note
2.)
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents