Uh" Malfunction Of System, Refrigerant System Address Undefined - Daikin R410As Service Manual

Vrv heat pump 50hz
Table of Contents

Advertisement

Si39-302
2.51 " UH "
Malfunction of System, Refrigerant System Address
Undefined
UH
Remote
Controller
Display
Applicable
All models of indoor units
RXYQ5~48M
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
!
Supposed
Causes
!
!
Troubleshooting
Troubleshooting
Improper connection of transmission wiring between outdoor unit and outdoor unit outside
control adaptor
Defect of indoor unit PC board
Defect of outdoor unit PC board (A1P)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is
electricity
being introduce for
the first time after
installationor after an indoor
or outdoorunit PC
board has been
replaced?
NO
Is
indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
YES
After fixing incorrect wiring,
push and hold the RESET
button on the outdoor unit
PC board for 5 seconds
Replace whichever is
defective.
Does a malfunction occur?
YES
Does
a "UH" malfunction occur
for all indoor units in
the system?
YES
Troubleshooting by Indication on the Remote Controller
Does
a malfunction
occur even after 12
YES
minutes elapses from the
time when electricity is
introducedto indoor
and outdoor
units?
YES
NO
NO
NO
NO
Normal
After fixing incorrect wiring,
push and hold the RESET
button on the master outdoor
unit PC board for 5 seconds.
∗ The unit will not run for up to
12 minutes.
Normal
Replace indoor unit PC board.
Replace outdoor unit PC
board (A1P).
(V2831)
217