4.2.49 User group selection (Pr. 160, Pr. 173 to Pr. 176)

Pr. 160 "user group read selection"
Pr. 173 "user group 1 registration"
Pr. 174 "user group 1 deletion"
Pr. 175 "user group 2 registration"
Pr. 176 "user group 2 deletion"
• Pr. 160 "user group read selection" is used to limit the parameters which may be read.
• From among all parameters, a total of 32 parameters can be registered to two different user groups.
The registered parameters may only be accessed for reading and writing.
Parameters other than those registered to the user groups cannot be read.
Parameter Number
160
173
174
175
176
<Examples of use>
(1) Parameter registration to user group (when registering Pr. 3 to user group 1)
Pr. 173 reading
(2) Parameter deletion from user group (when deleting Pr. 5 from user group 1)
Pr. 174 reading
(3) By setting the required value in Pr. 160, make the user groups valid or invalid.
Pr. 160 Setting
0
All parameters can be accessed for reading and writing (factory setting)
1
Parameters registered to user group 1 may only be accessed for reading and writing.
10
Parameters registered to user group 2 may only be accessed for reading and writing.
11
Parameters registered to user groups 1 and 2 may only be accessed for reading and writing.
Note: 1. Pr. 77, Pr. 160 and Pr. 991 values can always be read independently of the user group setting.
2. When Pr. 173 or Pr. 174 is read, the number of parameters registered to user group 1 appears.
When Pr. 175 or Pr. 176 is read, the number of parameters registered to user group 2 appears.
3. "0" set in the second digit of the 2-digit Pr. 160 setting is not displayed. However, it is displayed
when "0" is set in the first digit only.
4. When "9999" is set in Pr. 174 or Pr. 176, the parameters registered to the corresponding user
group is batch-deleted.
Pr. 162 to Pr. 165
Factory Setting
0
0
0
0
0
The number of parameters
Using the
registered for user setting
choose the parameter number
appears.
to be registered.
The number of parameters
Using the
registered for user setting
choose the parameter number
appears.
to be deleted.
Refer to Pr. 57.
Setting Range
0, 1, 10, 11
0 to 999
0 to 999, 9999
9999: Batch deletion
0 to 999
0 to 999, 9999
9999: Batch deletion
Flickering
1.5 s
key,
Pr. 3 is registered to user
group 1.
Flickering
1.5 s
key,
Pr. 5 is deleted from user
group 1.
Description
154
PARAMETERS
Remarks
Using the
move to the next parameter
to be registered.
Using the
registration.
Using the
choose the parameter to be
deleted.
Using the
deletion.
key,
key, make
key,
key, make