External Operation Mode (operation Using External Input Signals) - Mitsubishi Electric FR-A500 Instruction Manual

Transistorized inverter.
Hide thumbs

Advertisement

3.3.2

External operation mode (Operation using external input signals)

(1) Operation at 60Hz
<Connection example>
Frequency setting by voltage input
Frequency setting
potentiometer
0 to 10VDC
For details of each terminal, refer to page 13 .
Step
Power-on → Operation mode check
Switch power on and make sure that the operation command
indication "EXT" is lit.
1
(If it is not lit, press the
press the
Start
Turn on the start switch (STF or STR).
The operation status indication "FWD" or "REV" flickers.
2
Note: The motor does not start if both the forward and reverse
rotation switches are turned on.
If both switches are turned on during operation, the motor
decelerates to a stop.
Acceleration → Constant speed
Slowly turn the potentiometer (frequency setting potentiometer) full
clockwise.
3
The frequency shown on the display increases gradually to 60.00Hz.
Deceleration
Slowly turn the potentiometer (frequency setting potentiometer) full
counterclockwise.
4
The frequency shown on the display decreases gradually to 0.00Hz.
The motor stops running.
Stop
Turn off the start switch (STF or STR).
5
(2) External jog operation
Keep the start switch (STF or STR) on to perform operation, and switch it off to stop.
1) Set Pr. 15 "jog frequency" and Pr. 16 "jog acceleration/deceleration" time.
2) Set the external operation mode.
3) Switch on the jog signal. Keep the start switch (STF or STR) on to perform
operation.
Use any of Pr. 180 to Pr. 186 (input terminal function selection) to assign the
terminal used for the jog signal.
Frequency setting by current input
STF
STR
SD
10
Inverter
2
Current input
5
4 to 20mADC
Description
key to choose the operation mode and
MODE
key to switch to external operation.)
OPERATION/CONTROL
STF
STR
SD
AU *
Inverter
4
5
58
*Short terminals AU-SD
for current input.
Image
ON
FR-DU04
MON
Forward
rotation
Reverse
rotation
FR-DU04
MON
FR-DU04
MON
FR-DU04
MON
Forward
rotation
Reverse
rotation
OFF
<Connection example>
STF
STR
Inverter
JOG
SD
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD
Stop

Advertisement

Table of Contents

   Related Content for Mitsubishi Electric FR-A500

Comments to this Manuals

Symbols: 0
Latest comments:
  • Rajesh yadav Nov 23, 2017 01:03:
    electrical controling conction manual
  • TAtang Jan 03, 2017 11:22:
    Jalan sebentar terus muncul E,7 errlor
  • THAI Sep 28, 2015 08:47:
    MANUAL INVERTER MITSUBISHI a100 .thank you very much
  • sandeep Feb 15, 2014 09:20:
    good manual and it is very good to understand the contant of inverter and i lernt many things in this manual