4.2.28 Applied motor (Pr. 71)

Pr. 71 "applied motor"
Set the motor used.
Parameter
Factory
Number
Setting
71
0
<Setting>
• Refer to the following list and set this parameter according
to the motor used.
Pr. 71
Thermal Characteristics of Electronic Overcurrent Protection
Setting
0
Thermal characteristics of a standard motor
1
Thermal characteristics of a Mitsubishi constant-torque motor
Thermal characteristics matching a standard motor
2
5-point flexible V/F characteristics (Refer to page 125)
Thermal characteristics for advanced magnetic flux vector control of the Mitsubishi standard
20
motor SF-JR4P (1.5kW (2HP) or less)
3
Standard motor
13
Constant-torque motor
Mitsubishi general-purpose motor SF-JR4P
23
(1.5kW (2HP) or less)
4
Standard motor
14
Auto tuning data can be read or set anew.
Mitsubishi general-purpose motor SF-JR4P
24
(1.5kW (2HP) or less)
5
Standard motor
15
Constant-torque motor
6
Standard motor
16
Constant-torque motor
7
Standard motor
17
Constant-torque motor
8
Standard motor
18
Constant-torque motor
• For the 5.5K and 7.5K, the Pr. 0 and Pr. 12 settings are automatically changed depending on the Pr. 71
setting.
Pr. 71
0, 2, 3 to 8, 20, 23, 24
Pr. 0
3%
Pr. 12
4%
Note: 1. When "8888" or "9999" is set in Pr. 19, "2" cannot be set in Pr. 71. To set "2" in Pr. 71, set the
appropriate value (other than "8888" and "9999") in Pr. 19.
2. When "2" is set in Pr. 71, Pr. 100 to Pr. 109 are displayed on the parameter unit (FR-PU04). In
other settings, if any of Pr. 100 to Pr. 109 settings is changed, the new setting is not displayed in
the "Default parameter list" and "Set parameter list".
3. Refer to Pr. 96 for offline auto tuning.
4. Set any of "3, 7, 8, 13, 17 and 18" to perform offline auto tuning.
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
Setting Range
0 to 8, 13 to 18, 20, 23, 24
Select "offline auto tuning setting".
Read auto tuning data, settings can be
changed.
Star connection
Delta connection
Standard motor
Delta connection
1, 13 to 18
2%
2%
CAUTION
103
PARAMETERS
Related parameters
Pr. 0 "torque boost"
Pr. 12 "DC injection brake voltage"
Pr. 19 "base frequency voltage"
Pr. 60 "intelligent mode selection"
Pr. 80 "motor capacity"
Pr. 81 "number of motor poles"
Pr. 96 "auto tuning setting/status"
Pr. 100 to Pr. 109
(V/F frequency/voltage)
Standard
Motor constants can
be entered directly.
Direct motor constant
entry and offline auto
tuning
Motor
Constant
Torque
4

Advertisement

Table of Contents

Comments to this Manuals

Symbols: 0
Latest comments:
  • Rajesh yadav Nov 23, 2017 01:03:
    electrical controling conction manual
  • TAtang Jan 03, 2017 11:22:
    Jalan sebentar terus muncul E,7 errlor
  • THAI Sep 28, 2015 08:47:
    MANUAL INVERTER MITSUBISHI a100 .thank you very much
  • sandeep Feb 15, 2014 09:20:
    good manual and it is very good to understand the contant of inverter and i lernt many things in this manual