User Group Selection (Pr. 160, Pr. 173 To Pr. 176) - Mitsubishi Electric FR-A520-2.2K Instruction Manual

Transistorized inverter, high function & low acoustic noise
Hide thumbs Also See for FR-A520-2.2K:
Table of Contents

Advertisement

z

User group selection (Pr. 160, Pr. 173 to Pr. 176)

Pr. 160 "user group read selection"
Pr. 173 "user group 1 registration"
Pr. 174 "user group 1 deletion"
Pr. 175 "user group 2 registration"
Pr. 176 "user group 2 deletion"
From among all parameters, a total of 32 parameters can be registered to two different user groups.
The registered parameters may only be accessed for reading and writing.
Other parameters than those registered to the user groups cannot be read.
Parameter
Factory Setting
Number
160
0
173
0
174
0
175
0
176
0
<Examples of use>
(1) Parameter registration to user group (when registering Pr. 3 to user group 1)
Pr. 173 reading
1)
2)
FR-DU04
FR-DU04
CONTROL PANEL
Hz
SET
A
V
MON
EXT
PU
MON
REV
FWD
The number of parameters
registered for user setting
appears.
(2) Parameter deletion from user group (when deleting Pr. 5 from user group 1)
Pr. 174 reading
1)
2)
FR-DU04
FR-DU04
CONTROL PANEL
Hz
SET
A
V
MON
EXT
PU
MON
REV
FWD
The number of parameters
registered for user setting
appears.
(3) By setting the required value in Pr. 160, make the user groups valid or invalid.
Pr. 160 Setting
0
All parameters can be accessed for reading and writing (Factory setting)
1
Parameters registered to user group 1 may only be accessed for reading and writing.
10
Parameters registered to user group 2 may only be accessed for reading and writing.
11
Parameters registered to user groups 1 and 2 may only be accessed for reading and writing.
Note: 1. Pr. 77, Pr. 160 and Pr. 991 values can always be read independently of the user group setting.
2. When Pr. 173 or Pr. 174 is read, the number of parameters registered to user group 1 appears.
When Pr. 175 or Pr. 176 is read, the number of parameters registered to user group 2 appears.
3. "0" set in the second digit of the 2-digit Pr. 160 setting is not displayed. However, it is displayed
when "0" is set in the first digit only.
4. When "9999" is set in Pr. 174 or Pr. 176, the parameters registered to the corresponding user
group is batch-deleted.
Pr. 162 to Pr. 165 Î Refer to Pr. 57.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting Range
Remarks
0, 1, 10, 11
0 to 999
0 to 999, 9999
9999: Batch deletion
0 to 999
0 to 999, 9999
9999: Batch deletion
Flickering
1.5 seconds
3)
FR-DU04
CONTROL PANEL
CONTROL PANEL
Hz
Hz
A
A
V
V
EXT
PU
MON
EXT
PU
REV
FWD
REV
FWD
Using the [UP/DOWN] key,
choose the parameter number
to be registered.
Flickering
1.5 seconds
3)
FR-DU04
CONTROL PANEL
CONTROL PANEL
Hz
Hz
A
A
V
V
EXT
PU
MON
EXT
PU
REV
FWD
REV
FWD
Using the [UP/DOWN] key,
choose the parameter number
to be deleted.
Description
140
PARAMETERS
4)
5)
FR-DU04
FR-DU04
CONTROL PANEL
Hz
SET
A
V
MON
EXT
PU
MON
REV
FWD
Pr. 3 is registered to user
Using the [UP/DOWN] key,
group 1.
move to the next parameter
to be registered.
Using the [SET] key, make
registration.
4)
5)
FR-DU04
FR-DU04
CONTROL PANEL
Hz
SET
A
V
MON
EXT
PU
MON
REV
FWD
Pr. 5 is deleted from user
Using the [UP/DOWN] key,
group 1.
choose the parameter to be
deleted.
Using the [SET] key, make
deletion.
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD

Advertisement

Table of Contents
loading

Table of Contents