4.2.57 Output phase failure protection selection (Pr. 251)

Pr. 251 "output phase failure protection selection"
You can make the output phase failure protection (E.LF) function which stops the inverter output invalid if one
of the three phases (U, V, W) on the inverter's output side (load side) becomes open.
Parameter
Setting
Number
Range
251
0,1

4.2.58 Override bias/gain (Pr. 252, Pr. 253)

Pr. 252 "override bias"
Pr. 253 "override gain"
When override is selected in Pr. 73 "0 to 5V, 0 to 10V selection", the override range can be extended from
50%-150% to 0%-200% and set as desired.
Parameter Number
252
253
Minimum
Setting
Factory Setting
Increments
1
1
Minimum Setting
Setting Range
Increments
0 to 200%
0 to 200%
200
150
Pr. 252
100
Pr. 253
50
0
0V
Description
0: Without output phase failure protection
1: With output phase failure protection
Related parameters
Pr. 73 "0 - 5V / 0 - 10V selection"
Factory Setting
0.1%
50%
0.1%
150%
Factory setting
(50% to 150%)
2.5V
5V
(5V)
(10V)
Voltage across 2-5
167
PARAMETERS
4

Advertisement

Table of Contents

   Related Content for Mitsubishi Electric FR-A500

Comments to this Manuals

Symbols: 0
Latest comments:
  • Rajesh yadav Nov 23, 2017 01:03:
    electrical controling conction manual
  • TAtang Jan 03, 2017 11:22:
    Jalan sebentar terus muncul E,7 errlor
  • THAI Sep 28, 2015 08:47:
    MANUAL INVERTER MITSUBISHI a100 .thank you very much
  • sandeep Feb 15, 2014 09:20:
    good manual and it is very good to understand the contant of inverter and i lernt many things in this manual