Mitsubishi Electric FR-A500 Instruction Manual page 74

Transistorized inverter
Hide thumbs Also See for FR-A500:
Table of Contents

Advertisement

Func-
Parameter
tion
Number
Commercial power supply-inverter
135
switchover sequence output
terminal selection
136
MC switchover interlock time
137
Start waiting time
Commercial power supply-inverter
138
switchover selection at alarm
occurrence
Automatic inverter-commercial
139
power supply switchover frequency
Backlash acceleration stopping
140
frequency (Note 7)
Backlash acceleration stopping
141
time (Note 7)
Backlash deceleration stopping
142
frequency (Note 7)
Backlash deceleration stopping
143
time (Note 7)
144
Speed setting switchover
145
PU display language selection
Stall prevention operation level at
148
0V input
Stall prevention operation level at
149
10V input
152
Zero current detection level
153
Zero current detection period
150
Output current detection level
151
Output current detection period
Voltage reduction selection during
154
stall prevention operation
155
RT signal activated condition
156
Stall prevention operation selection
157
OL signal waiting time
158
AM terminal function selection
160
User group read selection
Automatic restart after instantaneous
162
power failure selection
163
First cushion time for restart
164
First cushion voltage for restart
Restart stall prevention operation
165
level
168
Maker setting parameters. Do not make setting.
169
170
Watt-hour meter clear
171
Actual operation hour meter clear
173
User group 1 registration
174
User group 1 deletion
175
User group 2 registration
176
User group 2 deletion
Name
Setting Range
0, 1
0 to 100.0 s
0 to 100.0 s
0, 1
0 to 60.00Hz, 9999
0 to 400Hz
0 to 360 s
0 to 400Hz
0 to 360 s
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
0 to 200%
0 to 200%
0 to 200.0%
0 to 1 s
0 to 200%
0 to 10 s
0, 1
0, 10
0 to 31, 100, 101
0 to 25 s, 9999
1 to 3, 5 to 14,
17, 18, 21
0, 1, 10, 11
0, 1
0 to 20 s
0 to 100%
0 to 200%
0 to 999
0 to 999, 9999
0 to 999
0 to 999, 9999
65
Minimum
Factory Setting
Setting
<EC Version>
Increments
1
0.1 s
0.1 s
1
0.01Hz
0.01Hz
0.1 s
0.01Hz
0.1 s
1
0.1%
0.1%
0.1%
0.01 s
0.1%
0.1 s
1
1
1
0.1 s
1
1
1
0.1 s
0.1%
0.1%
0


0
1
1
1
1
PARAMETERS
Refer
Customer
To
setting
Page:
0
144
1.0 s
144
0.5 s
144
0
144
9999
144
1.00Hz
84
0.5 s
84
1.00Hz
84
0.5 s
84
4
87
150%
82
200%
82
5.0%
150
0.5 s
150
150%
149
0
149
1
82
0
151
0
151
0
153
1
90
0
154
0
94
0 s
94
0%
94
150%
94
0
155
0
155
0
154
0
154
0
154
0
154
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents