4.2.52 Output terminal function selection (Pr. 190 to Pr. 195)

Pr. 190 "RUN terminal function selection"
Pr. 191 "SU terminal function selection"
Pr. 192 "IPF terminal function selection"
Pr. 193 "OL terminal function selection"
Pr. 194 "FU terminal function selection"
Pr. 195 "A, B, C terminal function selection"
You can change the functions of the open collector and contact output terminals.
Parameter
Terminal
Number
Symbol
190
RUN
191
SU
192
IPF
193
OL
194
FU
195
A, B, C
<Setting>
Refer to the following table and set the parameters:
Setting
Signal
Positive
Negative
Name
logic
logic
0
100
RUN
1
101
SU
2
102
IPF
3
103
OL
4
104
FU
5
105
FU2
6
106
FU3
7
107
RBP
8
108
THP
9
109
PRG
10
110
PU
11
111
RY
12
112
Y12
13
113
Y13
14
114
FDN
15
115
FUP
16
116
RL
Factory-Set
Factory Setting
Terminal Function
0
Inverter running
1
Up to frequency
Instantaneous power
2
failure/undervoltage
3
Overload alarm
Output frequency
4
detection
99
Alarm output
Function
Inverter running
Up to frequency
Instantaneous power failure or
undervoltage
Overload alarm
Output frequency detection
Second output frequency
detection
Third output frequency
detection
Regenerative brake pre-alarm
Electronic overcurrent
protection pre-alarm
Programmed mode
PU operation mode
Inverter operation ready
Output current detection
Zero current detection
PID lower limit
PID upper limit
PID forward-reverse rotation
output
Setting Range
0 to 199, 9999
Operation
Output during operation when the inverter output
frequency rises to or above the starting frequency.
Refer to Pr. 41 "up-to-frequency sensitivity".
(Note 2)
Output when an instantaneous power failure or
undervoltage occurs.
Output while stall prevention function is activated.
Refer to Pr. 42, Pr. 43 (output frequency
detection).
Refer to Pr. 50 (second output frequency
detection).
Refer to Pr. 116 (third output frequency
detection).
Output when 85% of the regenerative brake duty
set in Pr. 70 is reached.
Output when the cumulative electronic
overcurrent protection value reaches 85% of the
preset level.
Output in the programmed mode. (Note 3)
Output when the PU operation mode is selected.
Output when the inverter can be started by
switching the start signal on or while it is running.
Refer to Pr. 150 and Pr. 151 (output current
detection).
Refer to Pr. 152 and Pr. 153 (zero current
detection).
Refer to Pr. 128 to Pr. 134 (PID control).
158
PARAMETERS
Related
parameter

Pr. 41

Pr. 22, Pr. 23,
Pr. 66, Pr. 148,
Pr. 149, Pr. 154
Pr. 42, Pr. 43
Pr. 50
Pr. 116
Pr. 70
Pr. 9
Pr. 79, Pr. 200
to Pr. 231


Pr. 150, Pr. 151
Pr. 152, Pr. 153
Pr. 128 to
Pr. 134