4.2.48 OL signal output timer (Pr. 157)
Pr. 157 "OL signal waiting time"
Use this parameter to set whether the overload alarm signal (OL signal) is output immediately or a preset
period of time after occurrence of an overload status.
Parameter
Factory Setting
Number
157
0
<Setting>
Refer to the following table and set the parameter:
Pr. 157 Setting
0
Output immediately.
0.1 to 25
Output after the set time (s) has elapsed.
9999
Overload alarm signal is not output.
Pr. 158
Refer to Pr. 54.
Setting Range
0 to 25 s, 9999
9999: No signal output
Overload status (OL output)
OL output signal
Description
153
Related parameters
Pr. 190 to Pr. 195
(output terminal function selection)
Remarks
Set time (s)
PARAMETERS
4