4.2.8

Starting frequency (Pr. 13)

Pr. 13 "starting frequency"
You can set the starting frequency between 0 and 60Hz.
Set the starting frequency at which the start signal is switched on.
Parameter
Factory Setting
13
0.5Hz
Note: The inverter will not start if the frequency setting signal is less than the value set in Pr. 13 "starting
frequency".
For example, when 5Hz is set in Pr. 13, the motor will start running when the frequency setting signal
reaches 5Hz.
When the Pr. 13 setting is equal to or less than the Pr. 2 "minimum frequency" value,
note that merely switching on the start signal will start the motor at the preset
frequency if the command frequency is not input.
Setting Range
0 to 60Hz
CAUTION
78
Related parameters
Pr. 2 "minimum frequency"
Output frequency
(Hz)
60
Pr.13
0
Frequency setting signal (V)
Forward
ON
rotation
PARAMETERS
Time