4.2.15 Regenerative brake duty (Pr. 30, Pr. 70)

Pr. 30 "regenerative function selection"
Pr. 70 "special regenerative brake duty"
When making frequent starts/stops with a 7.5K or less inverter, use the optional "high-duty brake resistor"
(FR-ABR) to increase the regenerative brake duty.
Use the optional "high power factor converter (FR-HC)" to reduce harmonics, improve the power factor, or
continue the regenerative mode.
Parameter
Factory
Number
Setting
30
0
70
0%
<Setting>
(1) When using the built-in brake resistor, brake unit, power return converter
• Set "0" in Pr. 30.
The Pr. 70 setting is made invalid.
At this time, the regenerative brake duty is as follows:
*FR-A520-0.4K to 3.7K .......... 3%
*FR-A520-5.5K to 7.5K .......... 2%
*FR-A540-0.4K to 7.5K .......... 2%
(2) When using the high-duty brake resistor (FR-ABR)
• Set "1" in Pr. 30.
• Set "10%" in Pr. 70.
(3) When using the high power factor converter (FR-HC) or power regeneration
common converter (FR-CV)
1) Set "2" in Pr. 30.
2) Use any of Pr. 180 to Pr. 186 to assign the following signals to the contact input terminals.
• X10: FR-HC connection, FR-CV connection (inverter operation enable signal) (Note 3)
To make protective coordination with the high power factor converter (FR-HC) or power regeneration
common converter (FR-CV), use the inverter operation enable signal to shut off the inverter output.
Enter the RDY signal of the high power factor converter or the RDYB signal of the power regeneration
common converter.
• X11: FR-HC connection (instantaneous power failure detection signal)
When the computer link plug-in option (FR-A5NR) is used and the setting is made to hold the pre-
instantaneous power failure mode, use this signal to hold that mode. Enter the instantaneous power
failure detection signal of the high power factor converter.
3) The Pr. 70 setting is made invalid.
* Set "10" and "11" in any of Pr. 180 to Pr. 186 to allocate the terminals used to input the X10 and X11
signals.
Setting Range
Remarks
0 to 2
0 to 15%
0.4K to 1.5K
0 to 30%
2.2K to 7.5K
0%
11K or more
85
PARAMETERS
Related parameters
Pr. 180 to Pr. 186
(Input terminal function selection)
4

Advertisement

Table of Contents

   Related Content for Mitsubishi Electric FR-A500

Comments to this Manuals

Symbols: 0
Latest comments:
  • Rajesh yadav Nov 23, 2017 01:03:
    electrical controling conction manual
  • TAtang Jan 03, 2017 11:22:
    Jalan sebentar terus muncul E,7 errlor
  • THAI Sep 28, 2015 08:47:
    MANUAL INVERTER MITSUBISHI a100 .thank you very much
  • sandeep Feb 15, 2014 09:20:
    good manual and it is very good to understand the contant of inverter and i lernt many things in this manual