TRANSISTORIZED INVERTER
-INSTRUCTION MANUAL-
12-BIT DIGITAL INPUT
FR-A5AX

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric FR-A5AX

  • Page 1 TRANSISTORIZED INVERTER -INSTRUCTION MANUAL- 12-BIT DIGITAL INPUT FR-A5AX...
  • Page 2: Safety Instructions

    Thank you for choosing the Mitsubishi transistorized inverter option unit. This instruction manual gives handling information and precautions for use of this equipment. Incorrect handling might cause an unexpected fault. Before using the equipment, please read this manual carefully to use the equipment to its optimum.
  • Page 3 WARNING Any person who is involved in the wiring or inspection of this equipment should be fully competent to do the work. Always install the option unit before wiring. Otherwise, you may get an electric shock or be injured. Handle this option unit with dry hands to prevent an electric shock. Do not subject the cables to scratches, excessive stress, heavy loads or pinching.
  • Page 4 (3) Usage WARNING Do not modify the equipment. CAUTION When parameter clear or all parameter clear is performed, each parameter returns to the factory setting. Re-set the required parameters before starting operation. For prevention of damage due to static electricity, touch nearby metal before touching this product to eliminate static electricity from your body.
  • Page 5: Table Of Contents

    CONTENTS 1.PRE-OPERATION INSTRUCTIONS Unpacking and Product Confirmation ....................1 Packing Confirmation...........................1 Structure ..............................2 2.INSTALLATION Pre-Installation Instructions........................3 Installation Procedure ..........................3 Wiring..............................5 3.12-BIT DIGITAL INPUT Wiring Examples ..........................6 Terminals .............................8 4.PARAMETERS Parameter List............................9 Parameter Setting ..........................11 Instructions............................16 5.SPECIFICATIONS Specifications.............................18...
  • Page 6: Pre-Operation Instructions

    1.PRE-OPERATION INSTRUCTIONS 1.1 Unpacking and Product Confirmation Take the option unit out of the package, check the unit name, and confirm that the product is as you ordered and intact. Functions arailable differ between FR-A500(L)/F500(L) series and FR-V500 series, always check before using.
  • Page 7: Structure

    PRE-OPERATION INSTRUCTIONS 1.3 Structure Front view Mounting holes Rear view Mounting Mounting hole hole Terminal block screw size M3 Terminal FR-A5AX symbol Connector Option fixing holes...
  • Page 8: Installation

    2.INSTALLATION 2.1 Pre-Installation Instructions Make sure that the input power of the inverter is off. CAUTION With input power on, do not install or remove the option unit. Otherwise, the inverter and option unit may be damaged. 2.2 Installation Procedure (1) Securely insert the connector of the option unit far into the connector of the inverter.
  • Page 9 INSTALLATION Inverter (without cover) Option unit Accessory screw (2 pcs.) Slot 1 Inverter side connector Slot 2 Option fixing hook Option side Slot 3 connector The slots 1, 2, and 3 are provided with an option fixing hook. CAUTION 1. Only one type of option per inverter may be used. When two or more options are mounted, pri- ority is in order of slots 1, 2 and 3, the options having lower priority are inoperative.
  • Page 10: Wiring

    INSTALLATION 2.3 Wiring Route the wires so that they do not take up a lot of space in the control circuit terminal block of the option unit. During wiring, do not leave wire off-cuts in the inverter. They may cause a fault, failure or malfunction. Use the space on the left side of the control circuit terminal unit to route the wires.
  • Page 11: Bit Digital Input

    3.12-BIT DIGITAL INPUT 3.1 Wiring Examples (1)Relay contact signal input (2)Open collector signal input [BCD code] [BCD code] FR-A5AX AY40 type transistor output module FR-A5AX Number of Number of Number of Number of Number of Number of Read command PC *...
  • Page 12 12-BIT DIGITAL INPUT REMARKS 1. As the input signals are at low level, use two parallel micro signal contacts or a twin contact for relay contact inputs to prevent a contact fault. Micro signal contancts Twin contancts 2. A transistor of the following specifications should be selected for the open collector signal: Electrical characteris- tics of the transistor used •...
  • Page 13: Terminals

    12-BIT DIGITAL INPUT 3.2 Terminals Terminal Symbol Description Digital signal input terminals (frequency/speed setting signal terminals) X0 to X11 Used to input a 3-digit BCD (999 maximum) (refer to page 6) or 12-bit binary (FFFH maxi- mum) relay contact or open collector signal. Data read timing input signal Used when a digital signal read timing signal is necessary.
  • Page 14: Parameters

    4.PARAMETERS 4.1 Parameter List This option unit does not function if the parameter values are factory setting values. Set the following parameter values according to the application: 4.1.1 FR-A500(L)/F500(L) Series Parameter Setting Factory Setting Function name Number Range Setting Increments Bias 0 to 400Hz 0.01Hz...
  • Page 15 PARAMETERS 4.1.2 FR-V500 Series Parameter Setting Factory Setting Function name Number Range Setting Increments Bias 0 to 3600r/min 0r/min 0.1r/min BCD code input Gain 0 to 3600r/min, 9999 1500r/min 1r/min Bias 0 to 3600r/min 0r/min 0.1r/min Binary input Gain 0 to 3600r/min, 9999 1500r/min 1r/min Selection of digital input type and analog...
  • Page 16: Parameter Setting

    PARAMETERS 4.2 Parameter Setting (1) Input selection [Pr.304 "Selection of digital input type and analog compensation input enable / disable." ] You can select the digital input signal type and whether compensation for digital input by analog input is enabled or not. When the setting is "9999" (factory setting), the 12-bit digital input is invalid. Analog Compensation Input* Digital Input Compensation...
  • Page 17 PARAMETERS (2) Data read timing signal on-off selection (Pr.305) Pr.305 setting Description The set frequency data (set speed data) entered from the digital signal input terminals is always imported independently of whether the DY signal is on or off. Digital signal input directly changes output frequency.
  • Page 18 PARAMETERS (4) Gain adjustment [Pr.301], [Pr.303] The gain may be set in either of the following two ways: ! How to set the output frequency at the input signal of 999 (BCD code) or FFFH (binary) (The factory setting is 60Hz (1500r/min. for the FR-V500 series) for this input signal. ) Pr.301 Pr.303 Gain...
  • Page 19 PARAMETERS (5) Digital input unit selection (Pr.329) (available with the FR-V500 series only) When "9999" is set in Pr.301(BCD code input gain) or Pr.303(binary input gain), the increment when the digital signal is set as output speed can be set. Pr.329 setting Input Value Increments 0.1r/min...
  • Page 20 (6) Digital torque command (Pr.447, Pr.448) (available with the FR-V500 series only) ! When "9999" is set in Pr.304 and "4" in Pr.804 "torque command selection" (The parameter setting can be made only when the FR-A5AX is mounted on the inverter.), digital torque command of the FR-A5AX (12bit) is made valid.
  • Page 21: Instructions

    PARAMETERS 4.3 Instructions (1) Acceleration/deceleration time When the frequency is set with the digital input signal, the acceleration/deceleration time is the period of time required to reach the "acceleration/deceleration reference frequency" set in Pr. 20. This is the same as when using the analog signal input. (2) There are the following restrictions on the digital input signal: •...
  • Page 22 (FR-A5AX) mounted on the inverter, operation is performed at the frequency (speed), which is the sum of the BCD code input of the FR-A5AX and the auxiliary input from terminal 1, only when 2 or 3 is set in Pr. 304.
  • Page 23: Specifications

    5.SPECIFICATIONS 5.1 Specifications !Digital input signal type ... . 3-digit BCD code or 12-bit binary !Digital input signal selection ..From operation panel or parameter unit !Input current .
  • Page 24 REVISIONS *The manual number is given on the bottom left of the back cover. Print Date Revision Manual Number Sep., 1997 IB(NA)-66808-A First edition Jan., 2002 IB(NA)-66808-B Addition Adaptable inverters...