(3) Changing the control logic
The input signals are set to sink logic for the NA version, and to source Logic for the EC version.
To change the control logic, the jumper connector on the back of the control circuit terminal block must be
moved to the other position.
(The output signals may be used in either the sink or source logic independently of the jumper connector
position.)
1) Loosen the two installation screws in both ends of the control circuit terminal block. (The screws cannot be
removed.)
Pull down the terminal block from the back of the control circuit terminals.
2) Remove the jumper connector in the sink logic position on the back surface of the control circuit terminal
block and fit it in the source logic position.
EC version
3) Using care not to bend the pins of the control circuit connector, reinstall the control circuit terminal block
and fix it with the installation screws.
Note: 1. Make sure that the control circuit connector is fitted correctly.
2. While power is on, never disconnect the control circuit terminal block.
3. The sink-source logic change-over jumper connector must be fitted in only one of those positions.
If it is fitted in both positions at the same time, the inverter may be damaged.
NA version
22
INSTALLATION AND WIRING