4.2.27 Retry function (Pr. 65, Pr. 67 to Pr. 69)

Pr. 65 "retry selection"
Pr. 67 "number of retries at alarm occurrence"
Pr. 68 "retry waiting time"
Pr. 69 "retry count display erasure"
When an alarm occurs, the retry function causes the inverter to automatically reset itself to make a restart
and continue operation. You can select whether retry is made or not, alarms reset for retry, number of retries
made, and waiting time.
When you have selected automatic restart after instantaneous power failure, restart operation is performed at
the retry operation time which is the same of that of a power failure. (Refer to page 94 for restart function.)
Parameter
Factory Setting
Number
65
0
67
0
68
1 s
69
0
<Setting>
Use Pr. 65 to select alarms to be reset for retry.
Errors Reset for Retry
Display
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.IPF
E.UVT
E.FIN
E. BE
E. GF
E. LF
E.OHT
E.OLT
E.OPT
E.OP1
E.OP2
E.OP3
E. PE
E.PUE
E.RET
E.CPU
E. 1
E. 2
E. 3
E. 6
E. 7
E.MB1
E.MB2
E.MB3
E.MB4
E.MB5
E.MB6
E.MB7
E.P24
E.CTE
E.ECT
E.OSD
Note:
indicates the errors selected for retry.
Setting Range
0 to 5
0 to 10, 101 to 110
0 to 10 s
0
Setting
0
1
2
3
101
4
5
PARAMETERS
4

Advertisement

Table of Contents

Comments to this Manuals

Symbols: 0
Latest comments:
  • Rajesh yadav Nov 23, 2017 01:03:
    electrical controling conction manual
  • TAtang Jan 03, 2017 11:22:
    Jalan sebentar terus muncul E,7 errlor
  • THAI Sep 28, 2015 08:47:
    MANUAL INVERTER MITSUBISHI a100 .thank you very much
  • sandeep Feb 15, 2014 09:20:
    good manual and it is very good to understand the contant of inverter and i lernt many things in this manual