Pr. 157 "OL signal output waiting time"
Use this parameter to set whether the overload alarm signal (OL signal) is output immediately or a preset
period of time after occurrence of an overload status.
Parameter
Factory Setting
Number
157
0
<Setting>
Refer to the following table and set the parameter:
Pr. 157 Setting
0
Output immediately.
0.1 to 25
Output after the set time t (seconds) have elapsed.
9999
Overload alarm signal is not output.
Pr. 158 Î Refer to Pr. 54.
Setting Range
0 to 25 s, 9999
9999: No signal output
Overload status (OL output)
OL output signal
Description
139
Related parameters
Pr. 190 "RUN terminal function
selection"
Pr. 191 "SU terminal function selection"
Pr. 192 "IPF terminal function selection"
Pr. 193 "OL terminal function selection"
Pr. 194 "FU terminal function selection"
Pr. 195 "ABC terminal function
selection"
Remarks
Set time t (seconds)
PARAMETERS