u
F6 and F7: Serial Communications Option Card Settings
These parameters are to configure communication option cards and communication fault detection methods.
n
F6-01: Communications Error Option Selection
Determines drive operation if a communication error occurs.
No.
F6-01
Communications Error operation Selection
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
n
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
F6-02
External Fault from Comm. Option Selection
Setting 0: Always Detected
Setting 1: Detection During Run Only
n
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
No.
F6-03
External Fault from Comm. Option Operation Selection
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
n
F6-04: BUS Error Detection Time
Sets the delay time for a "bUS" error detection.
No.
F6-04
n
F6-10: CC-Link Node Address
Sets the node address of a CC-Link option board.
No.
F6-10
n
F6-11: CC-Link Communication Speed
Sets the communication speed for a CC-Link option card.
No.
F6-11
Settings:
F6-11
0
1
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Parameter Name
Parameter Name
Parameter Name
Parameter Name
Bus Error Detection Time
Parameter Name
CC-Link Node Address
Parameter Name
CC-Link Communication Speed
Communication Speed
156 kbps
625 kbps
5.6 F: Option Settings
Setting Range
0 to 3
Setting Range
0 or 1
Setting Range
0 to 3
Setting Range
0.0 to 5.0 s
Setting Range
0 to 63
Setting Range
0 to 4
F6-11
Communication Speed
3
4
Default
1
Default
0
Default
1
Default
2.0 s
Default
5
0
Default
0
5 Mbps
10 Mbps
155