E3: V/F Characteristics For Motor 2 - Omron V1000 User Manual

Compact vector control drive 200 v class three-phase input 0.1 to 15 kw, 200 v class single-phase input 0.1 to 4.0 kw, 400 v class three-phase input 0.2 to 15 kw
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

n
E2-11: Motor Rated Power
This parameter sets the motor rated power in kW. During Auto-Tuning the value must entered to parameter T1-02. If Auto-
Tuning completes successfully, the value entered will automatically be saved to E2-11.
No.
E2-11
n
E2-12: Motor Iron-Core Saturation Coefficient 3
This parameter sets the motor iron saturation coefficient at 130% of the magnetic flux.
No.
E2-12
u

E3: V/f Characteristics for Motor 2

These parameters set the V/f pattern used for motor 2.
switching motors.
n
E3-01: Motor 2 Control Mode Selection
Selects the control mode for motor 2. Motor 2 can not be used with OLV for PM.
No.
E3-01
Setting 0: V/f Control
Setting 2: Open Loop Vector Control
n
E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 like shown in
No.
E3-04
E3-05
E3-06
E3-07
E3-08
E3-09
E3-10
Motor 2 Minimum Output Frequency Voltage
E3-11
E3-12
E3-13
<1> Values shown here are for 200 V class drives. Multiply voltage values by 1.15 for U-spec drives. Double the value when using a 400 V class
drive.
<2> Default setting is determined by the control mode for motor 2.
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Parameter Name
Motor Rated Power
Parameter Name
Motor Iron-Core Saturation Coefficient 3
Parameter Name
Motor 2 Control Mode Selection
Parameter Name
Motor 2 Max Output Frequency
Motor 2 Max Voltage
Motor 2 Base Frequency
Motor 2 Mid Output Frequency
Motor 2 Mid Output Frequency Voltage
Motor 2 Minimum Output Frequency
Motor 2 Mid Output Frequency 2
Motor 2 Mid Output Frequency Voltage 2
Motor 2 Base Voltage
0.00 to 650.00 kW
Refer to Setting 16: Motor 2 Selection on page 164
Setting Range
5.5 E: Motor Parameters
Setting Range
Depending on
Setting Range
1.30 to 5.00
Setting Range
0 or 2
Figure
5.41.
40.0 to 400.0 Hz
<1>
0.0 to 255.0
0.0 to 400.0
0.0 to 400.0
<1>
0.0 to 255.0
0.0 to 400.0
<1>
0.0 to 255.0
0.0 to 400.0
<1>
0.0 to 255.0
<1>
0.0 to 255.0
Default
o2-04
Default
1.30
for details on
Default
0
Default
50.0 Hz
200.0 V
<1>
50.0 Hz
<2>
<2>
<2>
<2>
0.0 Hz
0.0 Vac
0.0 Vac
5
149