3.9

Main Frequency Reference

u

DIP Switch S1 Analog Input Signal Selection

The main frequency reference can either be a voltage or current signal input. For voltage signals both analog inputs, A1
and A2, can be used, for current signals A2 must be used.
When using input A2 as a voltage input, set DIP switch S1 to "V" (left position) and program parameter H3-09 to "0" (0
to +10 Vdc with lower limit) or "1" (0 to +10 Vdc without lower limit).
To use current input at terminal A2, set the DIP switch S1 to "I" (default setting) and set parameter H3-09 = "2" or "3" (4-20
mA or 0-20 mA). Set parameter H3-10 = "0" (frequency reference).
Note: If Terminals A1 and A2 are both set for frequency reference (H3-02 = 0 and H3-10 = 0), the addition of both input values builds the
frequency reference.
Voltage Input
0 to 10 V
Setting Value
V (left position)
I (right position)
No.
Parameter Name
Frequency ref. (current)
H3-09
terminal A2 signal level selection
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Table 3.12 Frequency Reference Configurations
Drive
+10.5 V
+V
20 mA current
Main speed
frequency reference
A1
(voltage input)
Main speed
A2
frequency reference
(current input)
AC
Frequency reference
common
Figure 3.25 DIP Switch S1
Table 3.13 DIP Switch S1 Settings
Current input (4 to 20 mA or 0 to 20 mA): default setting
Table 3.14 Parameter H3-09 Details
Selects the signal level for terminal A2.
0: 0 to +10 V, unipolar input (with lower limit)
1: 0 to +10 V, bipolar input (no lower limit)
2: 4 to 20 mA
3: 0 to 20 mA

3.9 Main Frequency Reference

Current Input
4 to 20 mA input
or
0 to 20 mA input
DI P Switch S1
V
I
Description
Voltage input (0 to 10 V)
Description
Drive
+10.5 V
+V
20 mA current
Main speed
A1
frequency reference
(voltage input)
Main speed
A2
frequency reference
(current input)
AC
Frequency reference
common
Setting
Default
Range
Setting
0 to 3
2
3
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents