Setting 1: Set User Initialization Values
The current parameter settings are saved as "User Initialization Values". Once o2-03 is set to 1 and the ENTER key is
pressed, the values are saved and the display returns to 0.
Setting 2: Clear User Initialization Values
All "User Initialization Values" are cleared. Once o2-03 is set to 2 and the ENTER key is pressed, the values are erased
and the display returns to 0.
n
o2-04: Drive Model Selection
Parameter o2-04 matches the control board to the drive hardware. Proper setting of o2-04 is important for optimal
performance and proper protection for the drive hardware. This parameter is configured at the factory and does not normally
require adjustment in the field. It is available primarily to accommodate control board replacement in the event of damage.
No.
o2-04
Note: 1.
Refer to Defaults by Drive Capacity (o2-04) and ND/HD (C6-01) on page 340
depending on the drive model selection.
2. Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate properly.
n
o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be used to input a frequency reference from the digital operator.
No.
o2-05
Frequency Reference Setting Method Selection
Setting 0: ENTER Key Required
Every change in the frequency reference setting on the digital operator has to be finalized by pressing the ENTER key
before it becomes effective.
Setting 1: ENTER Key Not Required
The output frequency changes immediately when the reference is changed by the UP and DOWN key on the digital operator.
The ENTER key does not need to be pressed. The frequency reference is saved five seconds after the Up or DOWN key
has been released.
n
o2-06: Operation Selection when Digital LCD Operator is Disconnected
Determines if the drive will stop when an external LCD operator is removed in LOCAL mode or with b1-02 set to 0.
Note: An LCD operator is available as an option. This setting is not applicable to the standard LED operator that comes with the drive.
No.
o2-06
Setting 0: Continue Operation
The operation is continued.
Setting 1: Trigger a Fault
The operation is stopped and an "oPr" fault is triggered. The motor coasts to stop.
n
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up when the Run command is set to be given from
the digital operator.
Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02/16 = 0).
No.
o2-07
Motor Direction at Power Up when Using Operator
Setting 0: Forward
Setting 1: Reverse
n
o2-09: Initialization Specification Selection
This parameter sets the regional specifications for the drive and should not be changed.
u

o3: Copy Function

Use o3 parameters to Read, Copy, and Verify the parameter settings to and from the drive.
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Name
Drive Model Selection
Name
Name
Digital Operator Disconnection Operation
Name
5.10 o: Operator Related Settings
Setting Range
Depending on drive
-
for a list of o2-04 settings and parameters that change
Setting Range
0 or 1
Setting Range
0 or 1
Setting Range
0 or 1
Default
size
Default
0
Default
0
5
Default
0
215