5.7 H: Terminal Functions

5.7

H: Terminal Functions

H parameters are used to assign functions to the external terminals.
u

H1: Multi-Function Digital Inputs

n
H1-01 to H1-06: Functions for Terminals S1 to S6
These parameters assign functions to the multi-function digital inputs. The settings 0 to 9F determine function for each
terminal and are explained below.
Note: If not using an input terminal or if using the through-mode, set that terminal to "F".
No.
Parameter Name
H1-01
Digital Input S1 Function Selection
H1-02
Digital Input S2 Function Selection
H1-03
Digital Input S3 Function Selection
H1-04
Digital Input S4 Function Selection
H1-05
Digital Input S5 Function Selection
H1-06
Digital Input S6 Function Selection
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.
Setting
0
3-Wire Sequence
1
LOCAL/REMOTE Selection
2
External Reference 1/2
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Drive Overheat Alarm (oH2)
C
Terminal A1/A2 Enable/Disable
F
Not used/Through Mode
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast-Stop (N.O.)
16
Motor 2 Selection
17
Fast-stop (N.C.)
18
Timer Function Input
19
PID Disable
1A
Accel/Decel Time Selection 2
1B
Program Lockout
1E
Reference Sample Hold
20 to 2F External Fault
30
PID Integral Reset
Setting 0: 3-Wire Sequence
When one of the digital inputs is programmed for 3-Wire control, that input becomes a forward/reverse directional input,
S1 becomes the Run command input, and S2 becomes the Stop command input.
The drive will start the motor when the Run input S1 is closed for longer than 50 ms. The drive will stop the operation
when the Stop input S2 is released for a brief moment. Whenever the input programmed for 3-Wire sequence is open, the
drive will be set for forward direction. If the input is closed, the drive is set for reverse direction.
Note: When 3-Wire sequence is selected the Run and Stop command must be input at S1 and S2.
160
Table 5.25 Digital Multi-Function Input Settings
Function
Setting
Range
1 to 9F
40: Forward Run Command (2-wire sequence)
1 to 9F
41: Reverse Run Command (2-wire sequence)
0 to 9F
24: External Fault
0 to 9F
14: Fault Reset
<1>
0 to 9F
3 (0)
: Multi-Step Speed Reference 1
<1>
0 to 9F
4 (3)
: Multi-Step Speed Reference 2
Page
Setting
160
31
PID Integral Hold
161
32
Multi-Step Speed Reference 4
161
34
PID Soft Starter Cancel
35
PID Input Level Selection
161
40
Forward Run/Stop (2-wire sequence)
41
Reverse Run/Stop (2-wire sequence)
161
42
Run/Stop (2-Wire sequence 2)
161
43
FWD/REV (2-Wire sequence 2)
44
Offset Frequency 1 Addition
162
45
Offset Frequency 2 Addition
162
46
Offset Frequency 3 Addition
162
60
DC Injection Braking Command
162
61
External Speed Search Command 1
162
62
External Speed Search Command 2
65
KEB Ride-Thru 1 (N.C.)
162
66
KEB Ride-Thru 1 (N.O.)
67
Communications Test Mode
163
68
High-Slip Braking
164
6A
Drive Enable
164
75
Up 2 Command
164
76
Down 2 Command
164
7A
KEB Ride-Thru 2 (N.C.)
165
7B
KEB Ride-Thru 2 (N.O.)
165
7C
Short-Circuit Braking (N.O.)
165
7D
Short-Circuit Braking (N.C.)
Forward/Reverse Detection (V/f Control with
165
7E
Simple PG Feedback)
165
7F
Bi-directional PID output enable
165
90 to 96 FDBs Digital Input 1 to 6
166
9F
FDBs Disable
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Default
Function
Page
166
166
166
166
166
166
167
167
167
167
167
167
167
168
168
169
169
169
169
169