LED Operator Display
The following simultaneous contradictory settings: C6-05 is greater than
6 and C6-04 is greater than C6-03 (carrier frequency lower limit is greater
than the upper limit). If C6-05 is less than or equal to 6, the drive operates
at C6-03.
Upper and lower limits between C6-02 and C6-05 contradict each other.
LED Operator Display
Scaling for the Pulse Train monitor is set to 0 (H6-07 = 0) while H6-06 is
not set to 101, 102, 105, or 116.
LED Operator Display
Parameter b1-03 = 9 (simple positioning stop) and
• Drive is not initialized to European settings (o2-09 is not 2)
• Dwell function is activated (b6-03 or b6-04 are not 0)
• the KEB function is activated (H1- = 65/66/7A/7B)
• Stall prevention during deceleration is enabled (L3-04 is not 0)
• Overvoltage suppression is enabled (L3-11 = 1)
• High slip braking is enabled (H1- = 68)
• An S-curve is applied to the deceleration ramp (C2-03 and C2-04 are not
0)
• PID output or frequency reference to bi-directional output frequency
reference is enabled (d4-11 = 1) and the drive is not initialized to
European settings.
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
oPE10
Cause
oPE11
Cause
oPE13
Cause
oPE14
Cause
6.6 Operator Programming Errors
V/f Data Setting Error
The following setting errors have occurred where: E1-04 is greater than
or equal to E1-06 is greater than or equal to E1-07 is greater than or equal
to E1-09.
Or the following setting errors have occurred: E3-04 is greater than or
equal to E3-06 is greater than or equal to E3-07 is greater than or equal
to E3-09.
Possible Solutions
Correct the settings for E1-04, -06, -07 and -09 (or E1-04, -06, -07, -09
for motor 2).
Error Name
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Possible Solutions
Correct the parameter settings.
Error Name
Pulse Monitor Selection Error
Incorrect setting of monitor selection for Pulse Train (H6-06).
Possible Solutions
Change scaling for the Pulse Train monitor or set H6-06 to 101, 102, 105,
or 116.
Error Name
Application Setting Error
Incorrect setting in combination with simple positioning stop or Bi-
directional output conversion.
Possible Solutions
Check the initialization mode in parameter o2-09. Correct the parameter
settings.