Omron V1000 User Manual page 310

Compact vector control drive 200 v class three-phase input 0.1 to 15 kw, 200 v class single-phase input 0.1 to 4.0 kw, 400 v class three-phase input 0.2 to 15 kw
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

No.
Name
Max Output
E1-04
Frequency
E1-05
Max Output
These parameters are only applicable when E1-03 is set to
<24>
Voltage
F. To set linear V/f characteristics, set the same values for
E1-07 and E1-09. In this case, the setting for E1-08 will be
E1-06
Base Frequency
disregarded. Ensure that the four frequencies are set
according to these rules:
Mid Output
E1-07
E1-04 ≥ E1-06> E1-07 ≥ E1-09
Frequency
E1-08
Mid Output
<24>
Frequency Voltage
Minimum Output
E1-09
Freq.
E1-10
Minimum Output
<24>
Freq. Voltage
E1-11
Mid Output
<26>
Frequency 2
E1-12
Mid Output
<24>
Frequency Voltage
<26>
2
E1-13
Base Voltage
<24>
Motor Rated
Sets the motor nameplate full load current in amperes (A).
E2-01
Current
Automatically set during Auto-Tuning.
Sets the motor rated slip in Hertz.
E2-02
Motor Rated Slip
Automatically set during rotational Auto-Tuning.
Motor No-Load
Sets the magnetizing current of the motor in Ampere.
E2-03
Current
Automatically set during rotational Auto-Tuning.
Number of Motor
Sets the number of motor poles. Automatically set during
E2-04
Poles
Auto-Tuning.
Motor Line-to-Line
Sets the phase-to-phase motor resistance in ohms.
E2-05
Resistance
Automatically set during Auto-Tuning.
Sets the voltage drop due to motor leakage inductance as a
Motor Leakage
E2-06
percentage of motor rated voltage.
Inductance
Automatically set during Auto-Tuning.
Motor Iron-Core
Sets the motor iron saturation coefficient at 50% of
E2-07
Saturation
magnetic flux. Automatically set during Auto-Tuning.
Coefficient 1
Motor Iron-Core
Sets the motor iron saturation coefficient at 75% of
E2-08
Saturation
magnetic flux. Automatically set during Auto-Tuning.
Coefficient 2
Sets the motor mechanical loss as a percentage of motor
rated power (kW). Adjust in the following circumstances:
Motor Mechanical
E2-09
When there is a large amount of torque loss due to motor
Loss
bearing friction.
When there is a large amount of torque loss.
Motor Iron Loss for
E2-10
Torque
Sets the motor iron loss in watts (W).
Compensation
Sets the motor rated power in kilowatts (kW).
E2-11
Motor Rated Output
Automatically set during Auto-Tuning. (1 HP = 0.746 kW).
Motor Iron-Core
Set to the motor iron saturation coefficient at 130% of
E2-12
Saturation
magnetic flux.
Coefficient 3
Automatically set during rotational Auto-Tuning.
Motor 2 Control
0: V/f Control
E3-01
Method
2: Open Loop Vector (OLV)
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Description
VACrms Out(V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09 E1-07
E1-06 E1-11 E1-04
Frequency (Hz)
E2: Motor Parameters
Use E2 parameters to set motor-related data.
E3: Motor 2 V/f Characteristics
Use E3 parameters to set the V/f pattern for a second motor.
B.2 Parameter Table
Control
Mode
Range
Def.
OL
V/f
V
40.0 to
50 Hz
400.0
S
S
<10>
<21>
200 V
0.0 to 255.0
S
S
<10>
50 Hz
0.0 to
S
S
<10>
E1-04
2.5 Hz
0.0 to
A
A
<2>
E1-04
16.0 V
0.0 to 255.0
A
A
<2> <12>
1.3 Hz
0.0 to
S
S
<2> <10>
E1-04
12.0 V
0.0 to 255.0
A
A
<2> <12>
0.0 to
0.0 Hz
A
A
E1-04
0.0 to 255.0 0.0 V
A
A
0.0 to 255.0 0.0 V
A
S
10 to 200%
of drive
rated
<57>
S
S
current
<27>
0.00 to
<57>
A
A
20.00
0 to less
<57>
A
A
than E2-01
2 to 48
4 poles
A
A
0.000 to
65.000
<57>
A
A
<37>
<57>
0.0 to 40.0
A
A
E2-07 to
0.50
A
0.50
E2-07 to
0.75
A
0.75
0.0 to 10.0
0.0%
A
0 to 65535
<57>
A
0.40 kW
0.00 to
S
S
<12>
650.00
1.30 to 5.00
1.30
A
0 or 2
0
A
A
Addr. Hex Pg.
PM
S
303
146
S
304
146
S
305
146
-
306
146
-
307
146
S
308
146
-
309
146
-
30A
146
-
30B
146
-
30C
146
30E
147
30F
147
310
147
311
148
312
148
313
148
314
148
315
148
316
148
317
148
318
149
328
149
319
149
B
309

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents