Alarm Register Contents - Omron V1000 User Manual

Compact vector control drive 200 v class three-phase input 0.1 to 15 kw, 200 v class single-phase input 0.1 to 4.0 kw, 400 v class three-phase input 0.2 to 15 kw
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

C.10 MEMOBUS/Modbus Data Table
001DH
Motor Overheat (PTC input) (oH3)
001EH
Digital Operator Connection (oPr)
001FH
EEPROM Write Error (Err)
0020H
Motor Overheat (PTC input) (oH4)
0021H
MEMOBUS/Modbus Communication Error (CE)
0022H
Option Communication Error (bUS)
0025H
Control fault (CF)
0027H
PROFIBUS-DP Option External Fault (EF0)
0028H
PID Feedback Loss (FbL)
0029H
Undertorque Detection 1 (UL3)
002AH
Undertorque Detection 2 (UL4)
u

Alarm Register Contents

The table below shows the alarm codes that can be read out from MEMOBUS/Modbus register 007FH.
Alarm Code
0001H
Undervoltage (Uv)
0002H
Overvoltage (ov)
0003H
Heatsink Overheat (oH)
0004H
Drive Overheat (oH2)
0005H
Overtorque 1 (oL3)
0006H
Overtorque 2 (oL4)
0007H
Run commands input error (EF)
0008H
Drive Baseblock (bb)
0009H
External Fault 3, input terminal S3 (EF3)
000AH
External Fault 4, input terminal S4 (EF4)
000BH
External Fault 5, input terminal S5 (EF5)
000CH
External Fault 6, input terminal S6 (EF6)
000DH
Reserved
000FH
Cooling Fan Error (FAN)
0010H
Overspeed (oS)
0011H
Excessive Speed Deviation (dEv)
0012H
PG Disconnected (PGo)
0013H
Digital operator connection fault (oPr)
0014H
MEMOBUS/Modbus Communication Error (CE)
0015H
Option Communication Error (bUS)
0016H
Serial Communication Transmission Error (CALL)
374
Table C.5 Alarm Register 007FH Contents
Fault Name
0093H
Control Circuit Fault (CPF18)
0094H
Control Circuit Fault (CPF19)
0095H
Hardware fault at power up (CPF20)
0096H
Hardware fault at communication start up (CPF21)
0097H
A/D Conversion Fault (CPF22)
0098H
PWM Feedback Fault (CPF23)
0099H
Drive capacity signal fault (CPF24)
0101H
Option compatibility error (oFA00)
0102H
Option not properly connected (oFA01)
0104H
Option Self-diagnostics Error (oFA03)
0105H
Option Flash Write Mode Error (oFA04)
Alarm Code
0017H
Motor Overload (oL1)
0018H
Drive Overload (oL2)
001AH
Option Card External Fault (EF0)
001BH
Motor Switch command input during run (rUn)
001DH
Serial Communication Transmission Error (CALL)
001EH
Undertorque Detection 1 (UL3)
001FH
Undertorque Detection 2 (UL4)
0020H
MEMOBUS/Modbus Test Mode Fault (SE)
0022H
Motor Overheat (oH3)
0027H
PID Feedback Loss (FbL)
0028H
PID Feedback Loss (FbH)
002AH
Drive Disabled (dnE)
002BH
PG Disconnected (PGo)
0034H
High Current Alarm (HCA)
0039H
External Fault (input terminal S1) (EF1)
003AH
External Fault (input terminal S2) (EF2)
003BH
Safe Disable Input (HbbF)
003CH
Safe Disable Input (Hbb)
003DH
Mechanical Weakening Detection 1 (oL5)
003EH
Mechanical Weakening Detection 2 (UL5)
0049H
FDBs Alarm (dWAL)
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Fault Name

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents