5.2 b: Application
The time for DC Injection Braking is determined by the value set to b2-04 and by the output frequency at the time the Run
command is removed. It can be calculated by:
Figure 5.7 DC Injection Braking Time Depending on Output Frequency
Note: If an overcurrent (oC) fault occurs during DC Injection Braking to stop, lengthen the minimum baseblock time (L2-03) until the fault no
longer occurs.
Setting 3: Coast to Stop with Timer
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. If a Run command
is input before the operation wait time t expires, the drive will not rotate the motor and the Run command will need to be
cycled before operation can occur.
Run Command
Output Frequency
The operation wait time t is determined by the output frequency when the Run command is removed and by the active
deceleration time.
106
Run Command
ON
Output Frequency
DC Injection Braking
Motor Speed
Figure 5.6 DC Injection Braking to Stop
DC Injection brake time
DC Injection braking time
b2-04× 10
b2-04
Output frequency when
10%
Stop command was entered
ON
Drive output voltage
interrupted
Figure 5.8 Coast to Stop with Timer
OFF
Minimum Baseblock Time (L2-03)
DC Injection Braking
DC Braking
Time at Stop
Current (b2-02)
(b2-04)*
b2-04 • 10 • Output frequency
=
Max. output frequency (E1-04)
100%
(Maximum output
frequency)
OFF
ON
Operation Wait Time t
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
OFF
ON