No.
Name
Enter the Yaskawa motor code for the PM motor being
used. Various motor parameters are automatically set based
on the value of this parameter.
Note: Set to FFFF when using a specialized or custom
motor. For all other motors:
Motor Code
E5-01
Selection (for PM
<25>
motor)
All motor parameters are reinitialized to factory settings
when this parameter is set.
Motor Rated
E5-02
Capacity (for PM
Sets the rated capacity of the motor.
<25>
motor)
E5-03
Motor Rated
Sets the motor rated current in amps.
<25>
Current
E5-04
Motor Poles
Sets the number of motor poles.
<25>
E5-05
Set the resistance for each motor phase in units of
Motor Resistance
<25>
0.001 Ω.
E5-06
Motor d Axis
Sets the d axis inductance in units of 0.01 mH.
<25>
Inductance
E5-07
Motor q Axis
Sets the q axis inductance in units of 0.01 mH.
<25>
Inductance
Set the induced phase peak voltage in units of 0.1 mV (rad/
s) [electrical angle].
Set this parameter when using a Yaskawa SSR1 series PM
E5-09
Motor Induction
motor with derate torque, or a Yaskawa SST4 series motor
<25>
Voltage Constant 1
with constant torque.
When setting this parameter, E5-24 should be set to 0. An
alarm will be triggered if both E5-09 and E5-24 are set to
0, or if neither parameter is set to 0.
Set the induced phase-to-phase rms voltage in units of 0.1
mV/(r/min) [mechanical angle].
Set this parameter when using a Yaskawa SMRA Series
SPM Motor.
E5-24
Motor Induction
When setting this parameter, E5-09 should be set to 0. An
<25>
Voltage Constant 2
alarm will be triggered if both E5-09 and E5-24 are set to
0, or if neither parameter is set to 0.
If E5-03 (Motor Rated Current) is set to 0, however, then
an alarm will not be triggered when both E5-09 and E5-24
are set to 0.
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control.
<4> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not = 0.
<10> Default setting value is dependent on parameter E5-01, Motor Code Selection.
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<21> Range upper limit is dependent on parameter E4-01 Motor 2 Rated Current.
<22> Parameter can be changed during run.
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<25> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<26> Parameter ignored when E1-11, Motor 1 Mid Output Frequency 2, and E1-12, Motor 1 Mid Output Frequency Voltage 2, are set to 0.0.
<27> Setting units for this parameter are determined by o2-04, Drive Model Selection. Less than 11 kW: 2 decimal points, 11 kW and above: 1
decimal point.
<37> Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller.
<38> If using a Yaskawa SMRA Series SPM Motor, the default setting is 1800 r/min.
<52> Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency Voltage 2, are set to 0.
<53> Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/f Control.
<57> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection.
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Description
E5: PM Motor Parameters
0 0 0 0
Motor Voltage Class
and Capacity
0: 1800 r/min Series
0: Pico Motor
1: 3600 r/min Series
(SMRA Series)
2: 1750 r/min Series
1: Derated Torque for IPM
3: 1450 r/min Series
Motors
4: 1150 r/min Series
(SSR 1 Series)
F: Special Motor
B.2 Parameter Table
Control
Mode
Range
Def.
OL
V/f
V
<12>
0000 to
−
−
FFFF
<38>
0.10 to 18.5
<10>
−
−
10 to 200%
of drive
rated
<4>
−
−
current
<27>
<10>
2 to 48
−
−
0.000 to
<10>
−
−
65.000
0.00 to
<10>
−
−
300.00
0.00 to
<10>
−
−
600.00
0.0 to
<10>
−
−
2000.0
0
0.0 to
−
−
<10>
2000.0
Addr. Hex Pg.
PM
S
329
152
S
32A
152
S
32B
152
S
32C
152
S
32D
153
S
32E
153
S
32F
153
S
331
153
S
353
153
B