No.
Name
Terminal A2 Signal Level
H3-09
Selection
Terminal A2 Function
H3-10
Selection
H3-11
Terminal A2 Gain Setting
<22>
H3-12
Terminal A2 Input Bias
<22>
Analog Input Filter Time
H3-13
Constant
<22> Parameter can be changed during run.
<40> The availability of certain parameters depends on the control method used.
H3-
Function
Setting
0
Frequency Bias
1
Frequency Gain
Auxiliary Frequency Reference (used as a
2
Multi-Step Speed 2)
4
Output Voltage Bias
7
Overtorque/Undertorque Detection Level
B
PID Feedback
C
PID Set Point
E
Motor Temperature (PTC input)
F
Not used/Through Mode
10
FWD Torque Limit
11
REV Torque Limit
12
Regenerative Torque Limit
15
FWD/REV Torque Limit
16
Differential PID Feedback
30/31
FBDs Analog Input 1/2
No.
Name
Multi-Function Analog
H4-01
Output Terminal AM
H4-02
Multi-Function Analog
<22>
Output Terminal AM Gain
H4-03
Multi-Function Analog
<22>
Output Terminal AM Bias
H5-01
Drive Node Address
<39>
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Description
Sets the input signal level for terminal A2.
0: 0 to +10 V (with lower limit)
1: 0 to +10 V (no lower limit)
2: 4 to 20 mA
3: 0 to 20 mA
Sets the function of terminal A2.
When terminal A2 is not used or is used as a through
terminal, this parameter must be set to "F".
Sets the level of the input value selected in H3-10 when 10
V (20 mA) is input at terminal A2.
Sets the level of the input value selected in H3-10 when 0 V
(0 or 4 mA) is input at terminal A2.
Sets the primary delay filter time constant for terminals A1
and A2. Used for noise filtering.
H3 Multi-Function Analog Input Settings
Max output frequency (E1-04).
Same value can be set using H3-02 and H3-10.
10 V = 100%
Maximum output frequency (E1-04)
Motor rated voltage (E1-05).
Open Loop Vector: Motor rated torque
V/f Control: Drive rated current
10 V = 100%
10 V = 100%
10 V = 100.00%
Motor rated torque
Motor rated torque
Motor rated torque
Motor rated torque
10 V = 100%
Depending on function.
Description
H4: Multi-Function Analog Outputs
Use H4 parameters to configure the multi-function analog output terminals.
Selects the data to be output through multi-function analog
output terminal AM.
Set the desired monitor parameter to the digits available in
U-. For example, enter "103" for U1-03.
When using this terminal in through mode or when not using
it at all, set "000" or "031".
Sets terminal AM output gain.
Maximum output voltage is 10 V.
Sets terminal AM output bias.
H5: MEMOBUS/Modbus Communications
Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network.
Selects drive station node number (address) for MEMOBUS/
Modbus terminals R+, R-, S+, S-. Cycle power for the setting
to take effect.
Range
0 to 3
Switch between current or voltage inputs by
using DIP switch S1-2 switch on the terminal
board.
0 to 31
<40>
-999.9 to
1000.0
-999.9 to
999.9
0.00 to 2.00 0.03 s A A A
Maximum Input Level Possible
Range
000 to 999
<40>
-999.9 to
999.9
-999.9 to
999.9
0 to 20 H
B.2 Parameter Table
Control
Mode
Addr.
Def.
Pg.
Hex
O
P
V/f
LV
M
2
A A A
417
180
0
A A A
418
180
100.0
A A A
419
180
%
0.0% A A A
41A
180
41B
180
Control
Mode
Pg.
OL
V/f
V PM
O
O
O
181
O
O
O
181
O
O
O
181
O
181
O
O
O
181
O
O
O
181
O
O
O
181
O
O
O
181
O
O
O
181
O
181
O
181
O
181
O
181
O
O
O
182
O
O
O
182
Control
Mode
Addr.
Def.
Pg.
Hex
V/f OL
P
V
M
102
A A A
41D
182
100.0
S
S
S
41E
182
%
0.0% A A A
41F
182
1F
A A A
425
358
319
B