Advertisement

No.
E5-04
Note: This parameter is not reset when the drive is initialized using A1-03.
n
E5-05: Motor Armature Resistance (PM OLV)
Set the resistance for each motor phase (not line-to-line resistance). When measuring the resistance manually make sure
to enter the resistance of one phase into E5-05.
No.
E5-05
Note: This parameter is not reset when the drive is initialized using A1-03.
n
E5-06: Motor d Axis Inductance (PM OLV)
Sets the d axis inductance in units of 0.01 mH.
No.
E5-06
Note: This parameter is not reset when the drive is initialized using A1-03.
n
E5-07: Motor q Axis Inductance (PM OLV)
Sets the q axis inductance in units of 0.01 mH.
No.
E5-07
Note: This parameter is not reset when the drive is initialized using A1-03.
n
E5-09: Motor Induction Voltage Constant 1 (PM OLV)
Set the induced phase peak voltage in units of 0.1 mV/(rad/s) [electrical angle]. Set this parameter when using an SSR1
series IPM motor with derated torque or an SST4 series motor with constant torque.
When E5-01 is set to "FFFF" use either E5-09 or E5-24 for setting the voltage constant.
No.
E5-09
Note: 1. Ensure that E5-24 = 0 when setting parameter E5-09. An alarm will be triggered, however, if both E5-09 and E5-24 are set 0, or if
neither parameter is set to 0.
2. This parameter is not reset when the drive is initialized using A1-03.
n
E5-24: Motor Induction Voltage Parameter 2 (PM OLV)
Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set this parameter when using
an SMRA Series SPM Motor.
When E5-01 is set to "FFFF" use either E5-09 or E5-24 for setting the voltage constant.
No.
E5-24
Motor Induction Voltage Parameter 2 (PM OLV)
Note: 1. Ensure that E5-09 = 0 when setting parameter E5-24. An alarm will be triggered, however, if both E5-09 and E5-24 are set 0, or if
neither parameter is set to 0.
2. This parameter is not reset when the drive is initialized using A1-03.
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Parameter Name
Number of Motor Poles
Parameter Name
Motor Armature Resistance
Parameter Name
Motor d Axis Inductance
Parameter Name
Motor q Axis Inductance
Parameter Name
Motor Induction Voltage Constant 1
Parameter Name
5.5 E: Motor Parameters
Setting Range
2 to 48
Setting Range
0.000 to 65.000 Ω
Setting Range
0.00 to 300.00 mH
Setting Range
0.00 to 600.00 mH
Setting Range
0.0 to 2000.0 mV/(rad/s)
Setting Range
0.0 to 2000.0 mV/(r/min)
Default
Depending on
E5-01
Default
Depending on
E5-01
Default
Depending on
E5-01
Default
Depending on
E5-01
Default
Depending on
E5-01
Default
5
Depending on
E5-01
153