Omron V1000 User Manual page 159

Compact vector control drive 200 v class three-phase input 0.1 to 15 kw, 200 v class single-phase input 0.1 to 4.0 kw, 400 v class three-phase input 0.2 to 15 kw
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

5.6 F: Option Settings
No.
<1>
F6-58
<1>
F6-59
<1>
F6-60
<1>
F6-61
<1> Valid from drive software version 1011 and later.
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value x 2
Example:
If the drive output frequency monitor (U1-02) is 50.0 and the scaling is set to F6-56 = 6, then the value in the AC/DC
Drive Object 2AH, Instance 1, Attribute 7 would be 500 x 2
n
F6-62: DeviceNet Heartbeat Interval
Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the Heartbeat function.
No.
<1>
F6-62
<1> Valid from drive software version 1011 and later.
n
F7-01 to F7-04: Ethernet IP Address 1 to 4
The combination of these parameters sets the IP address of an Ethernet option board if installed. The address is set like
F7-01.F7-02.F7-03.F7-04. The default address is 192.168.1.20.
No.
F7-01
F7-02
F7-03
F7-04
<1> Valid from drive software version 1011 and later.
n
F7-05 to F7-08: Ethernet Subnet Mask 1 to 4
The combination of these parameters sets the Subnet Mask of an Ethernet option board if installed. The mask is set like
F7-05.F7-06.F7-07.F7-08. The default setting is 255.255.255.0.
No.
F7-05
F7-06
F7-07
F7-08
<1> Valid from drive software version 1011 and later.
n
F7-09 to F7-12: Ethernet Gateway Address 1 to 4
The combination of these parameters sets the gateway address of an Ethernet option board if installed. The address is set
as F7-09.F7-10.F7-11.F7-12. The default address is 192.168.1.1.
No.
F7-09
F7-10
F7-11
F7-12
<1> Valid from drive software version 1011 and later.
n
F7-13: Ethernet Address Mode at Startup
Determines how the Ethernet option card IP address is set.
No.
F7-13
158
Parameter Name
DeviceNet Torque Scaling
DeviceNet Power Scaling
DeviceNet Voltage Scaling
DeviceNet Time Scaling
Scaling
Parameter Name
DeviceNet Heartbeat
Parameter Name
Ethernet IP Address 1
Ethernet IP Address 2
Ethernet IP Address 3
Ethernet IP Address 4
Parameter Name
Subnet Mask 1
Subnet Mask 2
Subnet Mask 3
Subnet Mask 4
Parameter Name
Gateway Address 1
Gateway Address 2
Gateway Address 3
Gateway Address 4
Parameter Name
Address Mode at Startup
Setting Range
-15 to 15
-15 to 15
-15 to 15
-15 to 15
6
= 32000.
Setting Range
0 to 10
Setting Range
0 to 255
0 to 255
0 to 255
0 to 255
Setting Range
0 to 255
0 to 255
0 to 255
0 to 255
Setting Range
0 to 255
0 to 255
0 to 255
0 to 255
Setting Range
0 to 2
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Default
0
0
0
0
Default
0
Default
<1>
192
<1>
168
<1>
1
<1>
20
Default
<1>
255
<1>
255
<1>
255
0
Default
<1>
192
<1>
168
<1>
1
<1>
1
Default
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents