3.8

I/O Connections

u

Sinking/Sourcing Mode Switch

Set the DIP switch S3 on the front of the drive to switch the digital input terminal logic between sinking mode and sourcing
mode; the drive is preset to sinking mode.
Set Value
SINK
SOURCE
n
Transistor Input Signal Using 0 V Common/Sink Mode
When controlling the digital inputs by NPN transistors (0 V common/sinking mode), set the DIP switch S3 to SINK and
use the internal 24 V power supply.
SOURCE
Figure 3.23 Sinking Mode: Sequence from NPN Transistor (0 V Common)
n
Transistor Input Signal Using +24 V Common/Source Mode
When controlling digital inputs by PNP transistors (+24 V common/sourcing mode), set the DIP switch S3 to SOURCE
and use an external 24 V power supply.
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
Table 3.11 Sinking/Sourcing Mode Setting
Figure 3.22 DIP Switch S3
SINK
Shielded cable
Forward run/stop
Reverse run/stop
External fault N.O.
Fault reset
Multi-speed step 1
Multi-speed step 2
Details
Sinking Mode (0 V common): default setting
Sourcing Mode (+24 V common)
DIP Switch S3
SINK
SOURCE
Drive
S1
S2
S3
S4
S5
S6
SINK
S3
SOURCE
SC

3.8 I/O Connections

+24V
3
55