Inverter Connection For Different Pulse Operation; Motor Connection; Motor Selection - Siemens LOHER DYNAVERT I 6SE03 Installation Instructions Manual

Table of Contents

Advertisement

Electrical connection

6.6 Motor connection

6.5.5

Inverter connection for different pulse operation

Converters equipped with inputs with higher pulse numbers are available for higher outputs
from approx. 500 kW; these inputs result in lower line harmonics.
Connect the converter to the line supply depending on the number of pulses used:
Table 6- 1
Number of
pulses used
6
12
24
The type code can be found on the rating plate.
6.6
Motor connection
6.6.1

Motor selection

As current-source DC link converter (current source), LOHER DYNAVERT I devices are suitable
for single-motor drives and, with some restrictions, also for multi-motor drives.
The converter must conduct a minimum current during operation. Individual motors can be
switched on and off as long as the current does not fall below this minimum current. The
connected motors must have a minimum no-load current of typically 20 % of the converter
rated current.
• During operation, it is not permissible to disconnect the motor and the converter from
each other. In the event of interruptions, the converter monitoring function responds:
"Overvoltage fault (OF)".
• If, for safety reasons, an isolating point is required between the converter and the motor,
when opening, a leading auxiliary contact at -X2:8 must shut down the converter.
• The converter can also be operated without additional reactors even if very long motor
cables are used.
• The voltage stress on the motor is higher than in the case of line operation; see the
specific technical data.
• Due to the non-sinusoidal current during converter operation, additional motor losses
occur. The continuous torque or the motor power must therefore be reduced compared to
direct line operation. Depending on the counter-torque curve, the lower degree of cooling
also has an effect at low speeds in the case of self-ventilated motors.
66
Line connection dependent on the number of pulses used
Can be recognized
Connection at the converter at –X1:U1, V1, W1
in the type code:
2J.A-...
Three phases
2J.F-...
Two secondary transformer systems each with three phases, i.e. a
2J.D-...
total of six phases.
Both systems must be phase offset by 30°, e.g. using transformer
vector group Dy5d6.
2J.G-...
Four secondary transformer systems each with three phases, i.e. a
total of twelve phases.
The four systems must each be phase offset by 15°, e.g. using two
transformers with vector groups Dy5,25d6,25 and Dy4,75d5,75.
Installation and Operating Instructions for LOHER DYNAVERT I Series 7
Operating Instructions, 10/2022, 4BS0745-002

Advertisement

Table of Contents
loading

Table of Contents