Siemens CPU 1513-1 PN Equipment Manual
Hide thumbs Also See for CPU 1513-1 PN:

Advertisement

Quick Links

Edition
11/2022
EQUIPMENT MANUAL
SIMATIC
S7-1500
CPU 1513-1 PN
6ES7513-1AM03-0AB0
support.industry.siemens.com

Advertisement

Table of Contents
loading

Summary of Contents for Siemens CPU 1513-1 PN

  • Page 1 Edition 11/2022 EQUIPMENT MANUAL SIMATIC S7-1500 CPU 1513-1 PN 6ES7513-1AM03-0AB0 support.industry.siemens.com...
  • Page 2 Introduction Safety instructions SIMATIC Product overview S7-1500 CPU 1513-1 PN Connecting up (6ES7513-1AM03-0AB0) Interrupts, error messages, diagnostics and system alarms Equipment Manual Technical specifications Dimensional drawing 11/2022 A5E40881673-AC...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Table Of Contents

    Rear view of the CPU......................28 Operating mode buttons....................29 Connecting up............................ Interrupts, error messages, diagnostics and system alarms.............. 34 Status and error display of the CPU..................34 Technical specifications........................38 Dimensional drawing.......................... 50 CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 5: Introduction

    Industry Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation (TIA) and Totally Integrated Power (TIP).
  • Page 6: Guide Documentation S7-1500/Et 200Mp

    • Equipment Manuals CPUs • Equipment Manuals Interface Modules • Equipment Manuals Digital Modules • Equipment Manuals Analog Modules • Equipment Manuals Communications Modules • Equipment Manuals Technology Modules • Equipment Manuals Power Supply Modules CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 7: Simatic Technical Documentation

    QR codes. The Industry Online Support gives you the option to get information on all topics. Application examples support you in solving your automation tasks. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 8 Online Support: Industry Online Support International https://support.industry.siemens.com/cs/ww/en/view/109742705 Watch this short video to find out where you can find the overview directly in Siemens Industry Online Support and how to use Siemens Industry Online Support on your mobile device: Quick introduction to the technical documentation of automation products per video ( https://support.industry.siemens.com/cs/us/en/view/109780491...
  • Page 9 Introduction 1.1 Guide documentation S7-1500/ET 200MP You can find the application examples on the Internet. (https://support.industry.siemens.com/cs/ww/en/ps/ae) CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 10: Safety Instructions

    Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 11: Product Overview

    Dynamic management of certi­ The web server certificate for HTTPS communic­ Flexible certificate management ficates ation can now also be managed via the OPC UA GDS mechanism, without separate download of the hardware configuration. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 12: Application

    You can find an overview of all new functions, improvements and revisions in the respective firmware versions on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109478459). Application SIMATIC S7-1500 is the modular control system for a wide variety of automation applications in discrete automation. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 13 The controller can be retrofitted with additional modules at any time to expand its range of tasks. High industrial suitability due to the high resistance to EMC, shock and vibration enable universal use of the SIMATIC S7-1500, S7-1500R/H and S7-1500T automation systems. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 14 The CPUs of the S7-1500R/H redundant system offer a high degree of reliability and system availability. A redundant configuration of the most important automation components reduces the likelihood of production downtimes and the consequences of component errors. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 15 Max. 4 (up to 100 kHz) Pulse Train Output (PTO output) Max. 4 (up to 100 kHz) Max. 4 (up to 100 kHz) Frequency output Up to 100 kHz Up to 100 kHz CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 16 The fail-safe CPUs are certified for use in safety mode up to: • Safety class (Safety Integrity Level) SIL 3 according to IEC 61508:2010 • Performance Level (PL) e and Category 4 according to ISO 13849-1:2015 or EN ISO 13849-1:2015 CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 17 C/C++ blocks for the user program * 50 MB of the integrated work memory is reserved for the function library of CPU runtime CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 18 The system cabling for digital signal modules enables fast and clear connection to sensors and actuators from the field (fully modular connection consisting of front connector modules, CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 19: Hardware Properties

    HMI via the configured connection. The CPU, STEP 7 and their HMI ensure data consistency without additional engineering steps. The maintenance work is easier. Hardware properties Article number 6ES7513-1AM03-0AB0 CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 20 (https://support.industry.siemens. In addition to the functions listed here, a multitude of com/cs/ww/en/view/109761758) other functions that are described in the SIMATIC S7-1500 Display Simulator are shown on the display. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 21: Firmware Functions

    Security with SIMATIC S7 control­ Web browser. Make sure that you take appropriate meas­ lers system manual ures (e.g. limiting network access, using firewalls) to pro­ (https://support.industry.siemens. tect the CPU from being compromised. com/cs/ww/en/view/90885010) CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 22 Isochronous mode reduces possible fluctu­ ations of the process reaction times to a minimum. Time- assured processing makes higher machine cycles pos­ sible. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 23 Speed-controlled axis for controlling a drive with speed specification • Positioning axis for position-controlled positioning of a drive • Synchronous axis to interconnect with a master value. The axis is synchronized to the master axis pos­ ition. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 24 • Convenient handling of passwords. STEP 7 reads the password automatically for the blocks. This saves you time. • Optimum block protection because the users do not know the password itself. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 25: Operating And Display Elements

    When the display is switched off, the LEDs continue to show the status of the CPU. For more information on the temperatures at which the display switches itself on and off, refer to the Technical specifications (Page 38). CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 26 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. Reference You will find detailed information on the individual display options, a training course and a simulation of the available menu commands in the SIMATIC S7-1500 Display Simulator (https://support.industry.siemens.com/cs/ww/en/view/109761758). CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 27: Front View Of The Cpu Without Front Panel And View From Below

    Figure 3-4  View of the CPU 1513-1 PN (without front panel) – front NOTE Removing the display Only remove the display if it is faulty. You can find information on removing and replacing displays in the S7‑1500, ET 200MP system manual (https://support.industry.siemens.com/cs/ww/en/view/59191792). CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 28: Rear View Of The Cpu

    The following figure shows the connection elements on the back of the CPU 1513-1 PN. ① Shield contact surface ② Plug-in connection for power supply ③ Plug-in connection for backplane bus ④ Fastening screw Figure 3-6  View of the CPU 1513-1 PN - rear CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 29: Operating Mode Buttons

    2nd time and remains con­ tinuously lit (this takes three seconds). After this, release the but­ ton. 3. Press the operating mode button STOP again within the next three seconds. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 30: Connecting Up

    1L+ and 2L+ as well as 1M and 2M are bridged internally Maximum 10 A permitted If the CPU is supplied by a system power supply, it is not necessary to connect the 24 V supply. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 31 The number range of the MAC addresses is sequential. The first and last MAC address are lasered on the rating plate on the right side of each CPU 1513-1 PN. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 32 X1 P2 X80 DC 24 V X1 P1R X1 P2R ① CPU with control and operating mode X80 24 V DC Infeed of supply voltage buttons ② Electronics 24 V DC supply voltage CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 33 SIMATIC memory card ERROR LED (red) PN X1 P1R PROFINET interface X1 port 1 MAINT LED (yellow) PN X1 P2R PROFINET interface X1 port 2 X1 P1, X1 P2 LED Link TX/RX Figure 4-2  Block diagram CPU 1513-1 PN CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 34: Interrupts, Error Messages, Diagnostics And System Alarms

    MAINT LED (yellow LED) ④ LINK RX/TX LED for port X1 P1 (yellow/green LED) ⑤ LINK RX/TX LED for port X1 P2 (yellow/green LED) ⑥ STOP ACTIVE LED Figure 5-1  LED display of the CPU 1513-1 PN (without front panel) CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 35 CPU carries out a program with active breakpoint. The program is presently moving from one break­ point to another. Firmware update is being performed. Startup (transition from STOP → RUN) LED off LED off LED flashes yellow/green CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 36 Note, however, that it is not possible to read the LED status of the LINK RX/TX LEDs on all S7-1500 CPUs. You can find additional information on the "LED" instruction in the STEP 7 online help. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 37 • The CPU is set to "STOP" mode using the display or programming device and not with the LED off STOP button on the device. • The CPU is in RUN mode. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 38: Technical Specifications

    Repeat rate, min. Input current   Current consumption (rated value) 0.73 A Current consumption, max. 0.9 A Inrush current, max. 1.15 A; Rated value I²t 0.5 A²·s Power   Infeed power to the backplane bus 10 W CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 39 Number of time alarm OBs • • Number of delay alarm OBs Number of cyclic interrupt OBs 20; With minimum OB 3x cycle of 250 µs • • Number of process alarm OBs CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 40 • Size, max. 16 kbyte Number of clock memories 8; 8 clock memory bit, grouped into one clock • memory byte Data blocks   Retentivity adjustable • • Retentivity preset Local data   CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 41 Hardware clock • • Backup time 6 wk; At 40 °C ambient temperature, typically Deviation per day, max. 10 s; Typ.: 2 s • Operating hours counter   • Number Clock synchronization   supported • CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 42 Updating times The minimum value of the update time also – depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 43 Protocols   PROFIsafe Number of connections   • Number of connections, max. 128; via integrated interfaces of the CPU and con­ nected CPs / CMs Number of connections reserved for • ES/HMI/web CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 44 2 kbyte; 1 472 bytes for UDP broadcast – – UDP multicast Yes; max. 78 multicast circuits DHCP • • SNMP • • • LLDP • Encryption Yes; Optional Web server   • HTTP Yes; Standard and user pages CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 45 – Basic256Rsa15, Basic256Sha256, Aes128Sha256RsaOaep, Aes256Sha256RsaPss User authentication "anonymous" or by user name & password – – GDS support (certificate management) – Number of sessions, max. – Number of accessible variables, max. 50 000 CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 46 Yes; Parallel online access possible for up to 5 engineering systems Status block Yes; Up to 8 simultaneously (in total across all ES clients) Single step Number of breakpoints Status/control   Status/control variable • CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 47 – – per output cam per cam track – – per probe Positioning axis • – Number of positioning axes at motion control cycle of 4 ms (typical value) CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 48   configuration / programming / header   Programming language   – – – – – GRAPH – Know-how protection   • User program protection/password protec­ tion Copy protection • • Block protection CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 49 Weight, approx. 336 g General technical specifications You can find information on the general technical specifications, such as standards and approvals, electromagnetic compatibility, protection class, etc., in the S7-1500, ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...
  • Page 50: Dimensional Drawing

    Always observe the specified dimensions for installation in cabinets, control rooms, etc. Dimensional drawings for CPU 1513-1 PN Figure A-1  Dimensional drawing of CPU 1513-1 PN, front and side views Figure A-2  Dimensional drawing of CPU 1513-1 PN, side view with front panel open CPU 1513-1 PN (6ES7513-1AM03-0AB0) Equipment Manual, 11/2022, A5E40881673-AC...

Table of Contents