Connecting The 3Rw55 And 3Rw55 Failsafe Soft Starters To The Main Circuit Connection (Line Side/Motor Side) - Siemens SIRIUS 3RW55 Equipment Manual

Soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW55:
Table of Contents

Advertisement

5.4 Connecting the 3RW55 and 3RW55 Failsafe soft starters to the main circuit connection (line side/motor side)

5.4
Connecting the 3RW55 and 3RW55 Failsafe soft starters to the
main circuit connection (line side/motor side)
Requirements
• Observe the conductor cross-sections and tightening torques in the data sheet or on the front
of the 3RW55 or 3RW55 Failsafe soft starter beneath the hinged cover.
• Note the required tools indicated on the front of the 3RW55 or 3RW55 Failsafe soft starter
beneath the hinged cover.
• If you use a bar connection, you require wrenches of widths A/F 13 and 17.
Size
Size 1
Size 2
Size 3
Size 4
Size 5
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before working on this device.
Procedure for screw connection - sizes 1 and 2
Illustration similar
• Connect connection 1/L1, 3/L2, 5/L3 to the supply system
• Repeat steps
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006
DANGER
/
for connection 2/T1, 4/T2, 6/T3 with the motor.
Article No.
3RW551.-....
3RW552.-....
3RW553.-....
3RW554.-....
3RW555.-....
Connecting
Tightening torque
2 ... 2.5 Nm
4.5 ... 6 Nm
10 ... 14 Nm
14 ... 24 Nm
20 ... 35 Nm
and tighten the screws
.
75

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirius 3rw55 failsafe

Table of Contents