Download Print this page

Specifications - Mitsubishi Electric GT1155HS-QSBD Manual

Graphic operation terminal

Advertisement

1. Features
1) Improved monitoring performance and connectivity to FA devices
- Two types of display modes are provided: 256-color display and monochrome display. In the monochrome display, 16 scales are used to improve the display.
- High speed monitoring through high speed communication at maximum of 115.2kbps.
- Multiple languages are displayed using the Unicode2.1-compatible fonts and beautiful characters are drawn using the TrueType and high quality fonts.
- High speed display and high speed touch switch response.
2) More efficient GOT operations including screen design, startup, adjustment, management and maintenance works
- The display screen of the display unit is created using a drawing software for PC (GT Designer2 Ver2.18U or later/GT Designer3 Ver1.01B or later).
- The 3MB user memory is included as standard.
- CF card interface is included as standard.
- The USB connector interface is included as standard.
3) Enhanced support of FA device setup tools
- Transferring or monitoring the sequence programs using the personal computer connected to GOT is available, during direct connection to A, QnA, L, Q, or FX series
PLC CPU (FA Transparent function).
2. Part Name
2.1 Front Panel
(1)
(3)
F1
F2
F3
F4
F5
F6
GRIP SW
(12)
(11) (10)
(9)
(8)
No
Name
(1)
Keylock switch (2-position SW)
Switch for external direct wiring (independent contact)
(2)
Emergency stop switch
Switch for external direct wiring (independent contact)
(3)
Logo (2 places)
Removable
(4)
Display section
Displays the utility screen and the user creation screen.
(5)
Touch panel
For touch switch operation on the utility screen and the user creation screen.
Operation switch name sheet installation
(6)
Place (concave shape) where the operation switch name sheet (created by user) is installed.
place
(7)
Operation switch name sheet cover
Transparent cover to fix the operation switch name sheet (created by user) (removed when a sheet is inserted).
(8)
Display LED for grip switch
Display LED for grip switch (green) (lighting control from display section)
For external connection cable connection (for PLC, switch and power supply external wiring)
(9)
External interface connector
(connector: round 32 pins, male)
(10)
Operation switch (6 switches)
Switch for external direct wiring (independent contact)
(11)
Display LED for operation switch (6 LEDs)
Display LED for operation switch (green) (lighting control from display section)
Lit in green
Lit in orange
(12)
POWER LED
Blinks in orange/green : Blown back light bulb.
Not lit
For the PC connection, refer to the following.
(2)
(3)
(4)(5)
(6)(7)
Operation switch name sheet (prepared by the user)
installation example

Specifications

: Power is correctly supplied.
: Screen saving and backlight not lit.
: Power is not supplied.
GT11 Handy GOT User's Manual
2.2 Back Panel
Environmental protection back cover closed
(1)
(2)
(1)
(3)
(3)
(4)
(7)
(5)
(6)
No
Name
Specifications
Hook for mounting a
Hook for mounting a neck strap (must be prepared by
(1)
neck strap
the user)
Hook for hanging on
(2)
Hook when the Handy GOT is used hanging on walls.
walls
E n v i r o n m e n t a l
For opening and closing the environmental protection
(3)
p r o t e c t i o n b a c k
back cover (drop prevention screw)
cover screw
Opened and closed when the PLC communication
E n v i r o n m e n t a l
type is changed (RS-422
RS-232, before shipping:
(4)
p r o t e c t i o n b a c k
RS-422), the option function board is mounted, or the
cover
battery is replaced.
Used to hold the Handy GOT in hand by putting a
(5)
Hand strap
hand under the strap. Length adjustable.
Model, consumption current, serial No., Hardware/
(6)
Rating plate
Firmware version is indicated.
(7)
Grip switch
Switch for external direct wiring (independent contact)
3. Specifications
3.1 General Specifications
Item
Display section
0 to 40C
Operating ambient
temperature
Other than Display section 0 to 40C
Storage ambient temperature
-20 to 60C
Operating ambient humidity
10 to 90% RH, non-condensing (The wet bulb temperature is 39C or less.)
Storage ambient humidity
10 to 90% RH, non-condensing (The wet bulb temperature is 39C or less.)
Conforms to JIS
Vibration resistance
B3502 and
IEC61131-2
Shock resistance
Conforms to JIS B3502, IEC 61131-2 (147 m/s
Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electro conductive dust particles and
Operating atmosphere
must be no direct sunlight. (Same as for saving)
*1
2000 m (6562 ft) max.
Operating altitude
*2
 or less
Overvoltage category
Pollution degree
*3
2 or less
Cooling method
Self-cooling
*1 Do not use or store the GOT under pressure higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this instruction may cause a malfunction.
When the air inside the control panel is purged by pressurization, the surface sheet may be lifted by high pressure. As a result, the touch panel may be difficult to press,
and the sheet may be peeled off.
*2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the
machinery within the premises. Category  applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the
raged voltage of 300 V is 2500 V.
*3 This index indicates the degree to which conductive material is generated in the environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
Environmental protection back cover opened
(8)
(9)
(10)
(11)
(12)
(13)
(14)
Option function board installed
No
Name
Specifications
(8)
Battery holder
GT11-50BAT type battery holder
GT11-50BAT type battery. For storing clock data,
(9)
Battery
alarm history and recipe data.
C o n n e c t o r
f o r
(10)
For GT11-50BAT type battery connection
battery connection
(11) RS-232 interface
Connector for PLC communication using RS-232
Interface cable connector for PLC communication
Cable connector for
Connector for either (11) or (13) and for selection of
(12)
PLC communication
the PLC communication type. (Connected to RS-422
before shipping.)
(13) RS-422 interface
Connector for PLC communication using RS-422
Connector for option
Connector for mounting the GT11-50FNB type option
(14)
function board
function board
For the connection to the controller, microcomputer board or PC, refer to the
following.
GT11 Handy GOT User's Manual
Specifications
Frequency
Acceleration
Half-amplitude
5 to 9Hz
--
3.5mm
Under intermittent
vibration
9 to 150Hz
9.8m/s
2
5 to 9Hz
--
1.75mm
Under continuous
vibration
9 to 150Hz
4.9m/s
2
2
, 3 times each in X, Y and Z directions)
Sweep Count
--
10 times each in X,
Y and Z directions
--

Advertisement