Installation, Operations, Service & Maintenance
WARNING
Connecting a high-voltage battery (80 V or higher) to a low-range charger
(24 V – 48 V) may damage the charger.
Use voltage-keyed connectors on the chargers and batteries if your facility has
mixed battery voltages.
CAUTION
Use only copper wires.
CAUTION
Every ProCore Edge is assembled and programmed for each
customer's specific needs. Webasto recommends that you contact
Webasto Technical Support before making any modifications and/or
additions (such as modules) to your ProCore Edge.
NOTE
Three- and five-bay cabinets have field wiring terminal blocks that can
accept a input wire gauge range from 10 to 14 AWG (6–2.5 mm
• The minimum and maximum screw-tightening is 22.2 in-lb
• DC output power cables are provided with the charger.
• Anderson Euro, SB or SBX connectors are used.
• For more information, contact WCSI Customer Support at
The 10-bay cabinet has field wiring terminal blocks that can accept
a input wire gauge range from #10 AWG to #4 AWG. Refer to the
Torque Specifications Label on page 33 for the appropriate torque
value for the screws for each wire size.
Part Number 5911110 A02
(2.5 Nm) and 26.4 in-lb (3 Nm) of torque, respectively.
1-866-767-4242.