Bennett 3000 Series Operation Manual page 47

Hide thumbs Also See for 3000 Series:
Table of Contents

Advertisement

Volume Calibration (Most
Steps
Common)
• Key in the test
measuring can
volume size
• Press Enter.
6
• For example, if 5
gallons, key in
until the display
shows: 5,0
The Main Display will show: rEADY
7
Lift the nozzle and the
pump handle (if applicable).
8
Dispense fuel into the test measuring can.
Stop when the volume display is as close as possible to
the test can size entered in step six.
9
No need to stop precisely on the correct quantity, the
software will calculate the result correctly using the
amount dispensed.
3000 Series Operation Manual
Calibration Procedure
Percentage Calibration
+/-
Press
to change
the error entry mode
from Volume Units
(TCUS) to Percentage
Units (TCPC).
Key in the test
measuring can volume
size
Press Enter.
For example, if 5
gallons, key in until the
display shows: 5,0
Lift the nozzle and the pump
handle (if applicable).
Menu code 27 continued
Back to TOC
Setup and Programming
Existing Calibration Value
Press ↑ to bypass the
test can prompt.
The main retail display
will show:
PC Err
1A 0.00
Volume only display
will show:
1A 0.00
Key the correct value,
verify it is shown on
the Main Display,
press +/- to make the
value negative.
Press Enter.
The calibration value
entered should now
appear on the Display.
Not Required
Not Required
43