3.29 MENU CODE 27: ELECTRONIC CALIBRATION
IMPORTANT: Prior to calibrating the meter to the 719 Control Board, thoroughly purge the air from
the hydraulic lines by dispensing 50-100 gallons of fuel through the system, see Section 2.1
Dispensing Fuel.
• Dispenser meter test calibration values are factory set. The factory test values for each meter
are also written in marker on the meter housing.
• Final calibration is required on site.
• If a dispenser has no values entered for the meters (refer to Menu Code 99) attempting to
dispense fuel will produce Calibration Error 70, see Section 4.11 Error Codes.
• All programming in Menu Codes six (6) and four (4) must be setup prior to calibration.
NOTE: The factory test values for each meter are written in marker on the meter housing.
Three options are available for calibrating the meter to the 719 Control Board, see the Calibration
Option table below.
• Chose options one (1) or two (2) when using a proving test can that matches the option.
• Chose option three (3) when the calibration values are already known (typically used when
replacing a 719 Control Board).
Select the calibration option below which applies to your situation:
Calibration Option
1. Volume
2. Percentage
3. Direct Percentage Overwrite
Meter options:
Meter Options
Bennett SB-100
FPP High Flow Electronic
3000 Series Operation Manual
Utilizes a volumetric proving test can (cubic inches, cubic centimeters,
milliliters, etc.). The dispenser automatically converts and stores the volume
entry into a percentage.
Utilizes a percentage-based proving test can.
The percentage value is already known and is keyed in by the technician.
Standard Calibration
Procedure
Electronic
Electronic
Menu code 27 continued
Back to TOC
Description
Optional Calibration
Procedure
Mechanical
N/A
Setup and Programming
41