Zo1 - Zoning 1 Setup; Ztm - Zoning Time Setup; L - Number Of Lifts Setup - ECD 100-194 EN81 Manual

Table of Contents

Advertisement

E E P R O M S E T T I N G S
01: 00000001 (Level 8)
ZO1 – Zoning 1 setup
Extension of ZON
80: 10000000 (Level 9)
40: 01000000 (Level 10)
20: 00100000 (Level 11)
10: 00010000 (Level 12)

ZTM - Zoning time setup

This sets the amount of time prior to zoning to the "LOB" or "ZON" setting
To disable zoning set "LOB" and "ZON" to "00"
Zone timer starts after doors close with no further demand
The time is set in 10s increments
06: 00001000 = 60s
0a: 00001010 = 100s, "1 minute 40 seconds"
12: 00010010 = 180s, "3 minutes"

#.L - Number of Lifts setup

This sets the number of lifts in the group
All lifts within the group must be set to the same value
01: 00000001 (1 Lift)
02: 00000010 (2 Lifts)
03: 00000011 (3 Lifts)
04: 00000100 (4 Lifts)
05: 00000101 (5 Lifts)
06: 00000110 (6 Lifts)
Set value to number of lifts. (01 to 06 valid values)
See also Inputs-Outputs L.#