G R O U P
Section 3. Group
Group Connections and Communication
24Vdc and 0Vdc, up and down hall calls and HFS inputs MUST be looped between all elevators in the
group
Group serial communication uses RS485 3-wire system
Controllers in the group are linked at the Serial TX terminals, SX+, SX- and GND, using shielded 3 wire
serial cable
Install "Terminator" jumper link (above the LCD) on the last lift of the group only
The same version software (build date) must be used in all grouped controllers
See connection diagram below