Set XTM to 20. If the lift fails to slow down to levelling speed before reaching the floor, (fast speed relay is being
held up too long) reduce XTM value. If there is still too much creep (fast speed relay is being held up not long
enough) increase XTM time. Continue until desired result is obtained.
SD1 – Selective rear Doors setup, Levels 1-8
This sets the first floor of the selective front and rear doors.
Used in conjunction with FD1 and RD1
Selective Rear Door floors are treated as two separate floors requiring separate car and landing buttons. See 1(front)
and 1(rear) in table below
Setting Example: Refer to table below
SD1 40: 01000000 (Level 1 has selective front and rear doors)
FD1 D0: 11010000 (Level G, level 1(front) and level 2 have front doors)
RD1 40: 00101000 (Level 1(rear) and level 3 have rear doors)
This sets the levels for the rear doors to operate by turning on DZR output to 0V when lift answers call to
3C,3U,3D or 5C,5U,5D. See RD1.
FLOOR DESIG.
3
2
1
G
SD2 – Selective rear Doors setup, Levels 9-12
This sets the first floor of the selective front and rear doors.
Used in conjunction with FD2 and RD2
Setting example: 80: 10000000 (Level 9 & 10 selective)

SDX - Star Delta eXchange time setup

This sets the amount of time from star dropping out and delta picking up.
Set value for delay between star dropping and delta pulling in.
The time is set in 100ms increments.
08: 00001000 = 800ms
Set between 01 & 08
SDX – VF Drive setting 06,07,08 brake drop time
Traction lifts;
Valid only when EEPROM setting "DRV" is set to "06, 07, 08".
This sets the amount of time after a run for the brake drop in 10ms increments.
SDX value must be less than ST2 value
Set between 01 & ff

SFR - Short Floor Run setup

Note: this setting only works on MSL 00
This signal sets the short floor between 2 levels, so the controller will not set the fast speed relays (UF & DF).
SFR must be FF: 11111111 unless stated.
A setting for a short floor between levels 2 & 3 would be "9F", as follows.
12345678 - floors
10011111 = 9F
FRONT DOORS
2 (front) 4C, 4U, 4D
1 (front) 2C, 2U, 2D
G (front) 1C, 1U
REAR DOORS
3 (rear) 5C, 5D
1 (rear) 3C, 3U, 3D